4-2-6 Option Menu (opt)

aUg
FUNCTION
SETTING
REFERENCE
72

Process Time for Averaging Measured Value

The K3NR averages its measured value at regular preset intervals. Therefore,
when the K3NR is used to measure the rpm of a machine, for example, the value
indicated by the PV display will be stable without being influenced by the fluctua-
tion of the input pulse intervals or the rotation of the machine. If the input pulse
intervals are larger than the preset regular intervals, the K3NR calculates the
rpm using the input pulse intervals.
Setting
fast:
Averaged every 60 ms
0.5:
Averaged every 500 ms
1:
Averaged every 1 s
2:
Averaged every 2 s
4:
Averaged every 4 s
8:
Averaged every 8 s
16:
Averaged every 16 s
Default
fast
Without average processing
After average processing
Section 4-2
Input value
Display value
Input value
Display value