Output Test - Omron K3NR Operation Manual

Frequency/rate meter
Table of Contents

Advertisement

Output Test

6-2

Output Test

1, 2, 3...
1 second
Setting Mode
112
This function is convenient for checking a system to which the K3NR is con-
nected, especially when some inputs cannot be operated. The K3NR simulates
an input signal to check the output conditions.
Note The K3NR has output according to the simulated input in this menu. If there is
any device connected to the output of the K3NR, be sure that the output will not
have a negative influence on the device before testing the system.
• Follow the steps described below to perform the test.
1. While the K3NR is in RUN mode, press the Mode Key for more than one se-
cond to set the K3NR to the setting mode.
2. Repeatedly press the Mode Key until the test output test setting is dis-
played.
RUN mode
Setting values menu
sUset
Output test
test
3. Press the Mode Key for more than one second to display 0, which is a simu-
lated input value.
4. The simulated input value increases when the Up Key is pressed. Compara-
tive outputs are output according to the output pattern that has been preset.
5. The simulated input value decreases when the Shift Key is pressed. Com-
parative outputs are output according to the output pattern that has been
preset.
6. Press the Escape Key after testing. The test output test setting will be dis-
played again.
7. Press the Escape Key to return to the RUN mode.
• To change the simulated input value continuously, keep pressing the Up or
Shift Key.