Omron K3NR Operation Manual page 81

Frequency/rate meter
Table of Contents

Advertisement

Setting Mode
SETTING
EXAMPLE
1, 2, 3...
Follow the steps described below to set the process time for averaging measured value
to 4 s.
1. Press the Mode Key for more than one second while the opt option menu is
displayed. The aUg process time for averaging measured value setting will
appear.
2. Press the Shift Key to display present set value fast for changing. The
PROG indicator will flash.
3. Repeatedly press the Up Key until 4 is displayed. The setting will be vali-
dated automatically if no change is made for five seconds. The aUg process
time for averaging measured value setting will be displayed again.
Note Press the Mode Key to enter the displayed setting immediately. The
next parameter will be displayed.
When no operation is executed for five seconds
Set Value LED Display Model
Set Value LED Display Model
Set Value LED Display Model
Set Value LED Display Model
Set Value LED Display Model
Section 4-2
Basic Model
Basic Model
Basic Model
Basic Model
Basic Model
73

Advertisement

Table of Contents