4.6.5

Forced flue connection type C13 and C33

In an installation with a vertical or horizontal forced flue, it is essential
always to ensure that emissions do not trouble the immediate vicinity
of the combustion by-product outlet.
No regular presence of physical persons, height of the emissions
greater than 2 metres, no windows nearby, etc...
Refer to the chapter in the technical manual on the "rule on
installing sealed appliance terminals with a total output of less
than or equal to 70 kW, installed in a boiler room and using gas
fuels".
Installation of the combusted gas discharge and air supply
ducts
Models
C230-85
C230-130
C230-170
C230-210
+ = length up to 30 metres (consult us for longer lengths)
- = not possible
Ø (mm)
Alu 150
R = D
PPS 160
R = D
03/10/2012 - 300015171-001-01
Ø D (mm)
150
160
150
160
150
160
150
160
Elbow 90°
Elbow 45°
6.4
1.7
5.0
1.4
- The flue gas duct must be airtight and watertight and must be
constructed in such a way as to allow the discharge of
condensates.
- The horizontal sections need to be constructed with a gradient of 5
mm per metre.
- By way of an example, the table below gives the dimension L
according to the connection diameters and according to concept
(see below table).
Vertical forced flue
Horizontal forced flue
Dimension L includes the air duct and the
flue gas discharge duct in metres
50
37
16
14
At each additional elbow of 90° or 45°, subtract the length given
in the following table.
Length
Tee
Straight conduits
6.4
5.0
C 230 ECO
0.5
0.9
35