Setting The 0-10 Volt Input Function Of Scb-10 - DeDietrich AMC Pro 45 Service Manual

Control panel & high efficiency wall-hung gas boiler
Hide thumbs Also See for AMC Pro 45:
Table of Contents

Advertisement

Tab.23
Zone function settings explanation
Zone setting
0 = Disable
1 = Direct
2 = Mixing Circuit
3 = Swimming pool
4 = High Temperature
5 = Fan Convector
6 = DHW tank
7 = Electrical DHW
8 = Time Program
9 = ProcessHeat
10 = DHW Layered
11 = DHW Internal tank
7.4

Setting the 0-10 Volt input function of SCB-10

Tab.24
button > Installation Setup > SCB-10 > 0-10 volt input > Parameters
Code
Display text
EP014
SCB func. 10V PWMin
EP030
Min Setp Temp 0-10V
EP031
Max Setp Temp 0-10V
EP032
Min Setp Power 0-10V
EP033
Max Setp Power 0-10V
EP034
Min Setp Volt 0-10V
EP035
Max Setp Volt 0-10V
7725087 - v.01 - 06062019
Explanation
Removes the circuit display, the circuit is not used, but its pump output can be used as a
status output.
Setting to manage a heating pump on the selected zone, cooling is not possible.
Setting to manage a valve and a pump with the flow sensor, in heating or cooling (exam­
ple underfloor heating).
Setting to manage the pool heat pump according to the flow sensor (if the sensor is
present) and also the pool filter pump.
Setting to manage a pump, heats 365 days with program time, no stop in summer
Setting to manage a pump, to warm and refresh
Setting to manage a pump and a sensor for domestic hot water
Setting to manage a pump, a sensor and to use the valve connector to control a relay for
the electric resistance of the tank. When switching to summer mode the tank automatical­
ly switches to electric.
Setting to create a time schedule on the pump connectors.
Setting to manage a pump, heats 365 days 24/24, no stop in summer, priority on all cir­
cuits. The boiler will remove all protections to produce maximum power in a minimum of
time
Setting to manage domestic hot water with 2 sensors, a tank top sensor (Tsyst 1 or 2)
triggers the load and the bottom sensor of the tank (Tdhw) triggers the stop of the charge.
Setting to manage domestic hot water for boilers with internal tank.
There are three options for the 0-10 Volt input control of the SCB-10 print:
disable the input function.
the input is temperature based.
the input is heat output based
Description
Smart Control Board function 10 Volt PWM
input
Sets the minimum set point temperature for 0
- 10 volts for the Smart Control Board
Sets the maximum set point temperature for 0
- 10 volts for the Smart Control Board
Sets the minimum set point power for 0 - 10
volts for the Smart Control Board
Sets the maximum set point power for 0 - 10
volts
Sets the minimum set point voltage for 0 - 10
volts for the Smart Control Board
Sets the maximum set point voltage for 0 - 10
volts
7 Installation examples
Range
0 = Off
1 = Temperature control
2 = Power control
0 °C - 100 °C
0.5 °C - 100 °C
0 % - 100 %
5 % - 100 %
0 V - 10 V
0 V - 10 V
AMC Pro
29