Connection To A Type B23 / B23P Chimney - DeDietrich C 230 ECO Installation And Service Manual

Gas fired condensing boiler
Hide thumbs Also See for C 230 ECO:
Table of Contents

Advertisement

4.6.4

Connection to a type B23 / B23p chimney

- Abide by prevailing strandards and instructions, particularly the
Order of 27 April 2009 amending the Order of 2 August 1977.
- Particularly the order of 22 October 1969 (FRANCE)
- DTU 24.1 - Flue gas system fittings(FRANCE)
- On traditional installations, the fresh air required for combustion
comes directly from the room in which the boiler has been installed.
- A nozzle is provided for connection to the duct.
- The flue gas duct must be airtight and watertight and must be
constructed in such a way as to allow the discharge of
condensates.
- The horizontal sections need to be constructed with a gradient of 5
mm per metre.
- The chimney must be lined.
- At the lowest points, provide a siphon for the discharge of
condensates.
- By way of an example, the table below gives the dimension L
developed in the flue gas discharge duct according to the
connection diameters and according to concept (see below table).
Installation of the combusted gas discharge duct
Duct without elbows
03/10/2012 - 300015171-001-01
Boiler type
C230-85
C230-130
C230-170
C230-210
+ = Lengths up to 50 metres (more than this: consult us)
- = not possible
At each additional elbow of 90° or 45°, subtract the length given in
the following table.
Ø (mm)
PPS 110 R = 1/2D
Alu 150
R = D
PPS 160
R = D
- With a terrace installation, it is essential to provide two low
ventilation vents diagonally opposite each other in order to prevent
vacuums in the boiler room caused by wind eddies.
C 230 ECO
Max. total length developed in the flue
Ø (mm) +
gas discharge duct in metres (L)
Material
(B23P)
PPS 110
27
Flex 110
14.5
Alu 150
+ 50
PPS 160
+ 50
PPS 110
Flex 110
Alu 150
+ 50
PPS 160
+ 50
PPS 110
Flex 110
Alu 150
45
PPS 160
+ 50
PPS 110
Flex 110
Alu 150
27
PPS 160
43
Length
Elbow 90°
Elbow 45°
Tee
4.9
1.1
5.6
6.4
1.7
6.4
5.0
1.4
5.0
8
4
-
-
-
-
Straight
conduits
0.5
0.5
0.9
33