Advertisement

5.4 Gas settings

The boiler is preset in the factory to operate on natural gas G20 (Gas
H). For operation on natural gas L and propane, it is necessary to
carry out a gas conversion and set CO
5.4.1

Checks

Carry out a check at low stage and at high stage on all boiler
versions (a check at low stage only on C 230-85 ECO and C
230-130 ECO). For controlling and setting, use a CO
(based on O
). Close the opening around the sensor when
2
taking the measurement.
5.4.2

Fan speed

Adjustment
Press the
key until #CONFIGURATION is displayed.
Press
successively until #BOILER is displayed, then
until MAX.VENT., MIN.VENT. and ST.VENT. are displayed.
If the boilers are in cascade, press the
with K3 control panels.
The parameters can be modified with the + and - keys.
44
.
2
analyser
2
key for the boilers fitted
C 230 ECO
For operation on propane, carry out the conversion using the optional
conversion kit.
See paragraph "Changing gas"
The nominal output and the CO
value must be reset.
2
03/10/2012 - 300015171-001-01