Advertisement

4.4.3

Connecting the condensate discharge pipe

Discharge condensation water directly into the main drain.
Given the degree of acidity (pH 3-5), use only plastic materials to
make the connection.
Fill the siphon with water. Make the connection to the main drain with
a visible flow connection.
Emplacement of the siphon
Siphon assembly
Filling the siphon
28
The discharge duct must have a minimum gradient of 30 mm/m. The
discharge of condensation water via the gutter is not authorised,
given the risk of frost and the damage to the materials usually used
for gutters.