9 Servicing
RPIM-(0.6-1.5)FSN4E - Ducted indoor unit
3 Remove the electrical box cover.
4 Remove the service cover.
The liquid and gas pipe thermistors are secured to the copper
piping by a special clamp.
•
Liquid pipe thermistor: covered with cork tape.
•
Gas pipe thermistor: covered with pipe insulation.
Nº
1
Location of the thermistor
?
N O T E
•
Black connector: liquid thermistor.
•
Yellow connector: gas thermistor.
9.8.4 Removal of the fan parts
Fan parts: fan motor, fan casing and duct.
1 Remove the rear cover as indicated in chapter
the inlet and outlet air
thermistors".
2 Remove the tape located in the centre of the casing.
3 Press the locks and remove half of the fan casing.
4 Remove the fixture support screws and carefully remove the
motor together with the fans.
5 Loosen the screws securing the fans to the motor shaft.
?
N O T E
If the fan casing is to be fully removed, remove the screws securing the
other half to the fan motor fixture.
Nº
1
Fan casing
2
Lock
3
Fan duct
4
Shaft
5
Fan motor
305
SMGB0099 rev.0 - 12/2016
Part
"9.8.2 Removal of
Part
9