6 Optional functions
Optional functions through Remote control
Elem.
Optional function
EA
Not available
Fan operation control at
Eb
cooling Thermo-OFF
Forced Thermo-ON
EC
stoppage at cooling
Ed
Not available
Automatic fan speed
EE
control
Automatic indoor fan
speed mode (supporting
High H)
Models
EF
RPI-FSN4E
RPIM-FSN4E(-DU)
RCD-FSN3
RCIM-FSN4(E)
F0
Not available
Automatic OFF timer
setting
Models
RCI-FSN4
RPC-FSN3
RPK-FSN3M
RPI-FSN4E
RPIM-FSN4E(-DU)
RCD-FSN3
F1
RCIM-FSN4(E)
Automatic OFF timer
setting
Models
RPI-FSN3(P)E
RPC-FSN3E
RPF(I)-FSN2E
Remote control main/sub
F2
setting
Automatic reset of setting
F3
temperature
(4)
F4
Automatic reset time
213
SMGB0099 rev.0 - 12/2016
Individual
Settings
setting
00
Not available
O
Use at 00 conditions
01
00
Not activated function
O
01
Low
02
Slow
00
Not activated function
O
01
Available
00
Not available
O
Use at 00 conditions
01
00
Not activated function
O
01
Activated function
00
Not activated function
O
01
Activated function
-
-
Not available
00
Not activated function
01
1 h
02
2 h
03
3 h
04-24
(04-24) h
0A
30 min
X
0B
90 min
0C
40 min
0D
45 min
0E
50 min
0F
55 min
00
Not activated function
01
1 h
02
2 h
X
03
3 h
04-24
(04-24) h
0A
30 min
0B
90 min
00
Main (Master Remote Control)
X
01
Sub (Slave Remote Control)
00
Not activated function
X
01
Activated function
30 minutes
00
(factory setting)
01
15 minutes
X
02
60 minutes
03
90 minutes
Setting conditions
This function decreases the unit fan
speed to reduce the spreading of
smells and humidity.
This function is used to force
stoppage when cooling is complete.
This function limits the unit operation
by automatically controlling the fan
speed when the room temperature is
close to the set temperature.
This function is used to set the
automatic timer to switch off when
the unit has been started by remote
control.
(Do not set the functions "0C"-"0F"
when two remote control switches
are used in the same remote control
group)
This function is used to set the
automatic timer to switch off when
the unit has been started by remote
control.
This function is used when two
remote controls are installed in a
system.
This function releases the fixed 
temperature setting after a certain
time to limit unit operations and save
energy.
This function is used to set the
automatic reset time with the
temperature setting
Description