6 Optional functions
Optional functions through Remote control
Elem.
Optional function
Fixing of operation as
b7
exclusive cooling mode
only
Automatic COOL/HEAT
b8
operation
b9
Fixing of fan speed
bA
Not available
Cooling temperature
bb
compensation due to
uneven load
bC
Not available
bd
Not available
bE
Not available
C1
Not available
C2
Not available
C3
Not available
Drain pump in
C4
heating mode
Static pressure selection
Models
RPI-FSN4E
RPIM-)FSN4E(-DU)
RPI-FSN3(P)E
Increasing fan speed
C5
Models
RPC-FSN3E
RPF(I)-FSN2E
RCI-FSN4
RPC-FSN3
RPK-FSN3M
RCD-FSN3
RCIM-FSN4(E)
Hi speed at heating
C6
Thermo-OFF
210
SMGB0099 rev.0 - 12/2016
Individual
Settings
setting
00
Not activated function
X
01
Activated function
00
Not activated function
X
01
Activated function
00
Not activated function
X
01
Activated function
"- -"
X
Not available
Permanent
Standard setting.
00
No compensation
It decreases the temperature
X
01
-1ºC
It decreases the temperature
02
-2ºC
00
Not available
Use at 00 conditions
01
00
Not available
Use at 00 conditions
01
00
Not available
Use at 00 conditions
01
00
Not available
Use at 00 conditions
01
"- -"
Not available
Permanent
00
Not available
O
Use at 00 conditions
01
00
Not activated function
O
01
Activated function
Standard static pressure (factory
00
set)
O
01
High static pressure
02
Low static pressure
00
Not available
01
Hi Speed 1
O
02
Hi Speed 2
00
Not activated function
O
01
Activated function
Setting conditions
This function is available to use
cooling mode only and to prevent
heating mode from being enabled.
This function allows the automatic
change from the cooling to the
heating mode for the units with the
same refrigerant cycle.
Once the unit fan speed has been
selected, this function prevents from
being modified from the remote 
control.
This function is used to obtain longer
cooling periods.
This function is used to activate the
drain pump in heating mode.
Not available for models:
RCIM-FSN4(E)
RCD-FSN3
This function is used to change the
static pressure of the RPI units from
the remote control.
(2)
This function is used to change the
indoor units fan speed installed in
high ceilings.
(2)
This function is used to increase
the fan speed when the thermostat
reaches the set temperature in
heating using function C5.
Description