Electrical Connection Of Rcim Units - Hitachi RCI-1.0FSN4 Service Manual

Table of Contents

Advertisement

4 Electrical and control settings
Unit electrical wiring and connection

For RCI-FSN4
Cord clamp
Wiring support plate
Electrical box
PCB
(Printed circuit
board)
Electrical box
cover
Firmly secure the cables using a tie inside the electrical box.
Cover the cables and the hole using a sealant to protect them from condensation and insects.
Test runs
!
C A U T I O N
Be careful during the test runs, as some of the safety functions remain disabled: the units operate for two hours without switching off
via the thermostat. The three-minute compressor protection is not enabled during the test.
Secure the rubber bushes to the panel using adhesive when the outdoor unit ducts are not used.
The compressor remains at a standstill during forced stoppage.

4.1.5 Electrical connection of RCIM units

Before proceeding to any electrical connection
1 Turn off the power supply switches before starting work and fit the appropriate locks and safety warnings.
2 Wait 5 minutes after turning off the power supply switches.
3 Check that the fans on the indoor and outdoor units are at a standstill before starting work.
?
N O T E
The electrical power for the unit must involve a specific power line, with an exclusive power control switch and residual current breaker,
installed in line with local or national safety regulations.
Check that the electrical power line has enough capacity to supply the unit. Its length, the cable diameter and their protection (sleeve
or jacket) must be appropriate for the unit.
For further information, always consider the current regulations in the country where the unit is to be installed.
!
C A U T I O N
Risk of fire: cables must never touch the refrigerant pipes, printed circuit boards (PCB), sharp edges or electrical components inside
the unit to avoid damaging them.
Loose connection terminals may lead to cable and terminal overheating. The unit may operate incorrectly, leading to a risk of fire.
Check that the cables are firmly secured to the connection terminals.
136
SMGB0099 rev.0 - 12/2016
Piping cover
Wiring connection hole
Screw for wiring
support plate under
piping cover
Screw
(for electrical box cover)
Earth
screw
Power source cable
(1~ 230V 50Hz)
(0.75 mm
)
2
Max current: 5 A
Remote control
switch cable
Transmission wiring (0.75 mm
Earth terminal
Terminal board (TB1)
Terminal board (TB2)
)
2
Electrical box