9 Servicing
RPC-(1.5-6.0)FSN3 - Ceiling type
Notes for Mounting Bearing
Mount the fixing plate for a flange bearing according to the following notes:
Align the shaft centers of the flange 1 and flange 2.
Insert washers between the flanges.
The tightening torque for bolts shall be 6N-m. This indoor unit utilizes the self-aligning bearing which enables the
self-alignment by reducing the alignment torque for the bearing. Therefore, if the tightening work is not performed 
correctly, an abnormal noise may occur.
Check that only the bearing body rotates and moves with the bolts tightened.

9.5.6 Removing Coupling (Except for RPC-1.5 and 2.0FSN3)

1 Open the air inlet grille downward according to
Air Filter and Air Inlet
Grille".
2 Remove the lower casing according to
motor".
3 Loosen 2 fixing screws for the coupling with a hexagon wrench 
and shift the coupling to the fan motor according to
Removal of the fan
motor".
4 Shift the shaft to the plate in the direction of the arrow (
remove the coupling from the fan motor (
Notes for Remounting Coupling
Tighten the fixing screws, inserting them into the grooves on the shaft.
Pay attention to the insertion direction of the coupling because the diameters of the shaft and the motor shaft are
different.
The coupling shall be located 24mm away from the fan motor.
285
SMGB0099 rev.0 - 12/2016
Shaft
Washer
Bearing
"9.5.1 Removing
"9.5.4 Removal of the fan
"9.5.4
1
). Then
2
).
Shaft
Shaft
Coupling
Coupling
Tighten the fixing screws,
Tighten the fixing screws, inserting them into 
inserting them into the grooves on the shaft.
the grooves on the shaft
Flange 1
Washer
Flange 2
The centers of the flange 1 
and 2 are out of alignment
24
Fan Motor
Fan motor
1
2
9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents