6 Optional functions
Indoor units input and output signals
Indication
o1
o2
o3
Component
Auxiliary relay (X2)
Contact (SS1) (x1) (example)
3-pin connector cable
Cable (control)
Voltage: 12 Vdc
Cable (power)
Voltage: 230 V
Recommendations for wiring installation
Keep the CN3 connector cables as short as possible.
Try not to pull on the cable along the power line. The cables should be laid separately at a distance of over 30 cm.
Cable crossing is feasible.
Where the cable along the power line is pulled, insert the cables through a metal pipe, earth one end of the pipe and
install a safety device such as an earth leakage breaker or smoke detector.
It is recommended to install safety devices such as an electric leakage breaker, etc, (because this is unattended
function).
Returning from optional function setting mode
Press "
" (return) to return to the normal mode (Operation Mode Indication).
201
SMGB0099 rev.0 - 12/2016
Connections
Manufacturer or specifications
Reduced power relay model
OMRON: MY1F or equivalent
Manual type
Optional part PCC-1A
(capable of connecting the connector
(JST XHP-3))
0.5 mm
2
2.0 mm
2
Remarks
Voltage between the relay
terminals 12 Vdc, 75 mA
Voltage between the contactor terminals
230 V, 5 mA
Five cables with connectors in one group
6