D7212GV3 | Program Entry Guide | 2.0
A# Perimeter Fault
Default:
0
Selection:
0, 1 to 24, A, B, or C
Activates when a Controlled Perimeter point (P##
Type 1) assigned to the specified area is faulted,
regardless of the armed state of the area. This relay
provides a steady output until all Perimeter points in
the area return to normal.
This relay does not activate on interior
faults. To detect all area point faults,
program all points as Perimeter points in
the area where this relay is assigned.
A# Silent Alarm
Default:
0
Selection:
0, 1 to 24, A, B, or C
This relay activates when a point assigned to the
specified area and programmed for P## Silent Bell
goes into alarm.

2.12.2 Panel-Wide Relays

The following eleven relay options activate when they
occur anywhere in the control panel. They are not
restricted by area boundaries.
AC Failure
Default:
0
Selection:
0, 1 to 24, A, B, or C
Activates when the control panel responds to an AC
power failure as programmed in AC Fail Time in
Section 2.4 Power Supervision on page 23. This
relay automatically resets when AC power restores.
Use this relay to create audible
annunciation. Enable the keypad's trouble
sounders for all applications except
commercial fire systems.
Battery Trouble
Default:
0
Selection:
0, 1 to 24, A, B, or C
Activates when battery voltage falls below 85% of
capacity (12.1 VDC) for a fully charged (13.8 VDC)
battery, or when the battery is in a missing condition.
This relay automatically resets when battery power
restores.
Use this relay to create audible
annunciation. Enable the keypad's trouble
sounders for all applications except
commercial fire systems.
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
Panel and Area Wide Parameters
Phone Fail
Default:
Selection:
Activates when a telephone line failure occurs. A time
must be entered in Ph Supv Time (refer to Section
2.2 Phone Parameters on page 9) for this relay to
activate. This relay resets automatically when restoral
of the phone line(s) occurs.
Comm Fail
Default:
Selection:
Activates when a control panel cannot communicate
a report after making ten attempts to each routing
destination. At the same time, COMM FAIL RG
shows at the keypad. This relay automatically resets
when a report is sent successfully.
Use this relay to report primary digital
report failure to an alternate
communication device.
Log % Full
Default:
Selection:
Enter the number of the relay that activates when the
log reaches the programmed percentage of its
capacity, as programmed in the Log % Full prompt.
This relay provides a steady output until a Get Log
and Set Pointer is executed from the remote
programming software (RPS).
Summary Fire
Default:
Selection:
Enter the number of the relay that activates when any
Fire point in the system (P## Type 0, P## Fire Yes)
enters into alarm. This relay provides a steady output
until all Fire points in the system return to normal.
Summary Alarm
Default:
Selection:
Enter the number of the relay that activates when a
Non-fire point enters into alarm. This relay provides a
steady output until the alarm is acknowledged by a
valid passcode, then cleared from alarm memory with
an acknowledgment at the keypad.
0
0, 1 to 24, A, B, or C
0
0, 1 to 24, A, B, or C
0
0, 1 to 24, A, B, or C
0
0, 1 to 24, A, B, or C
0
0, 1 to 24, A, B, or C