Panel And Area Wide Parameters; Phone - Bosch D7212GV3 Program Entry Manual

Table of Contents

Advertisement

D7212GV3 | Program Entry Guide |
2.0 Panel and Area Wide
Parameters
This section has twelve programming categories:

Phone

Phone Parameters
Routing
Area Parameters
Power Supervision
Printer Parameters
RPS Parameters
Miscellaneous
Area Parameters
Keypad
User Interface
Function List
Relay Parameters.
2.1
Phone
The control panel can dial as many as four different
telephone numbers when sending event reports.
Refer to Section 2.3 Routing on page 12 for
information about event report routing and
communication protocols.
Phone #
Default:
Blank
Selection:
Up to 24 characters
0 to 9
Numbers 0 through 9
C
2-sec pause
D
7-sec dial-tone detection
# or *
Used for the same purpose as
pressing this key on a telephone
keypad when manually dialing. For
example, an asterisk (*) may be
needed to access your long distance
service. Do not use these characters
when pulse dialing.
Blank
Control panel dials no phone number.
Programming this item Blank does
not disable phone routing. To disable
reporting to this phone, refer to
Section 2.3 Routing on page 12.
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
This is the telephone number the control panel dials
to contact the central station receiver when sending
event reports. This number is Phone 1 referred to in
the prompts in Section 2.3 Routing on page 12.
The control panel waits for a break in the dial tone
after dialing the first digit. If the control panel must
dial a digit (for example, 9) to access an outside line,
place a C before the phone number. The control
panel waits 2 sec and does not wait for the dial tone
break.
The control panel is programmed with a seven-sec
dial tone detect period. When a dial tone is detected
or the waiting period ends, the control panel begins to
dial. To extend the dial tone detect period, place a D
before the phone number. To insert a pause during or
after dialing, use C in the number sequence. For
example, if the control panel hangs up before it hears
2
the Modem IIIa
Ack tone from the central station
receiver, program extra Cs after the phone number.
The control panel waits on line for two extra seconds
for each C programmed.
Enter up to 24 of the characters shown in the Phone
# table to define dialing characteristics.
For SIA CP-01 Compliance
Call Waiting Disable
If the telephone system at the installation site uses
the Call Waiting feature, ensure that the primary
telephone reporting number is programmed to
disable Call Waiting.
If you program the primary phone number with a
sequence to temporarily disable Call Waiting
(typically *70 pause, but verify with the phone service
provider) followed by the phone number, you should
program the backup phone number without the Call
Waiting cancel sequence. If the subscriber cancels
Call Waiting without notifying their alarm installing
company, the control panel can still send reports
using the backup number.
Dialing a Call Waiting sequence on a
non-Call Waiting line prevents the system
from dialing the central station receiver
successfully.
Example: If the central station telephone
number is 555-1234, and the primary
Route Group destination is Phone 1,
program Phone 2 with the following
sequence: *70C5551234.