Sia Cp-01 Quick Reference; Cp--01 Compliance - Bosch D7212GV3 Program Entry Manual

Table of Contents

Advertisement

D7212GV3 | Program Entry Guide | 7.0
7.0

SIA CP-01 Quick Reference

Table 35: Programming the Control Panels for SIA CP--01 Compliance
Prompt Name
Phone #
Duress Type
Cancel Report
A# Exit Dly Time
A# Duress Enable
A# Exit Restart
A# Arm No Exit
A# Two Man Rule
A# Early Ambush
A# Exit Warning
A# Entry Warning
1
A# Burg Time
A# Alarm Bell
CC# Entry Tone
CC# Exit Tone
CC# Abort Display
CC# Cancel Display
Master Arm Inst
Perimeter Instant
L## Send Duress
L## Disarm
L## Passcode Disarm
P## Entry Delay
P## Alarm Abort
Abort Window
Passcode Length
Swinger Count
Remote Warning
Cross Point Time
P## Cross Point
1 The SIA allowed range is 1 min to 90 min. Must additionally comply with UL requirements, refer to section A# Burg Time.
2 L14 is the default duress user index.
3 The default for P## Alarm Abort is No for P3, P4, P5, and P22.
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
SIA CP-01 Quick Reference
Bosch Recommended Settings
for SIA CP-01 Compliance
(Prefix backup phone number with
Call Waiting disable command)
Option 3
Yes
45 sec to 255 sec
Yes
Yes or No
Yes or No
No
No
Yes
Yes
6 min to 90 min
1 to 128(64), A, B, C
Yes or No
Yes or No
Yes or No
Yes or No
{Blank}
{Blank}
[Blank] or E
[Blank] or E
[Blank] or E
30 sec to 240 sec
Yes or No
15 sec to 45 sec
3 to 6 digits
1 to 2 trips
Yes
5 to 255 sec
Yes or No
Shipping Default
{Blank}
0 (disabled)
Yes
60 sec
No
Yes
Yes
No
No
Yes
Yes
6 min
A (on-board alarm output)
Yes
Yes
Yes
Yes
{Blank}
{Blank}
2
E
2
E
2
E
30 sec
3
Yes
30 sec
Disabled
1 trip
Yes
20 sec
No
EN | 128
References
Page 8
Page 30
Page 31
Page 32
Page 33
Page 43
Page 43
Page 41
Page 42
Page 43
Page 44
Page 36
Page 70
Page 48
Page 49
Page 50
Page 50
Page 55
Page 55
Page 68
Page 61
Page 68
Page 83
Page 90
Page 124
Page 125
Page 125
Page 125
Page 127
Page 89

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents