D7212GV3 | Program Entry Guide | 2.0
L## Default Text
Default:
Refer to the program record sheet
Selection:
- or E
Function No.
Function Name
34
Default Text
Temporarily show the armed state of the area using
control panel default text, A# AREA # IS ON, A# NOT
READY, A# AREA # IS OFF, and A# ACCOUNT IS
ON.
L## Change Skeds
Default:
Refer to the program record sheet
Selection:
- or E
Function No.
Function Name
35
Change Skeds
Change skeds that can be edited.
Editing of skeds can be restricted by
programming S## Time Edit? to No.
L## Invisible Walk Test
Default:
Refer to the program record sheet
Selection:
-, or E
Function
Function Name
No.
36
Invisible Walk
Test
Test all points that are programmed to be invisible
and that are within the scope of the keypad without
sending reports to the central station. Invisible points
must be programmed P## Invisible Point as Yes.
This walk test mode can test 24-hour points and
controlled points.
Invisible Test? allows the user with this L## to start
an invisible walk test for all 24-hour interior and
posterior controlled points in the area to which this
keypad is assigned. When an invisible test is started,
one person can test invisible points without
assistance.
The following features are provided with the Invisible
Test Mode:
The display indicates exactly how many
invisible points are assigned to the area.
Battery and bell tests do not occur during this
walk test.
The keypad shows point text when invisible
points are tested.
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
Panel and Area Wide Parameters
Alternate Keystroke
[COMMAND][5][7]
Alternate Keystroke
2.10.7 Custom Functions
[COMMAND][5][2]
L## C Function 128 [through 131]
Execute the desired Custom Function.
Report Levels
Alternate
L## Force Arm
Keystroke
(Menu function
only)
A user with this authority level can Force Arm.
L## Area O/C
Generates Opening and Closing Reports if the area
where this authority level is assigned sends Opening
and Closing Reports.
The test ends when all points are tested, or if
the test times out after ten min of no activity.
Local event printing occurs without alarm
annunciation or reports sent to the central
station receiver.
The D1255 Keypad shows a sequential count
and text related to the point after each point
is activated and restored.
The keypad shows All PTS TESTED. An
All Points Tested Event is sent to the central
station receiver (if programmed) when the
last point is tested.
Walk Start and Walk End Reports are sent to
the central station receiver for the beginning
and end of the test (if programmed in phone
routing).
Default:
Refer to the program record sheet
Selection:
- or E
Function No.
Function Name
128 through
Enable Custom
13
Function 128
through 131
Default:
Refer to the program record sheet
Selection:
- or E
Default:
Refer to the program record sheet
Selection:
- or E
EN | 67