D7212GV3 | Program Entry Guide | 4.0
P## Relay Response Type
Default:
Refer to the program record sheet
Selection:
0 to 2
0
Point state does not affect the
operation of the corresponding relay.
1
Relay Follows Point: The relay
corresponding with this point
activates when the point is faulted to
any off-normal condition, even if the
point is bypassed. The relay
automatically resets when the point
returns to normal.
2
Relay Latches: The relay
corresponding with this point latches
when the point enters into an alarm
condition. This relay provides a
steady output until the alarm is
acknowledged by a valid passcode,
then cleared from alarm memory with
an acknowledgment from the keypad.
Use this option to cause a relay (1 to 24 for the
D7212GV3) to respond when a corresponding point
with the same number (1 to 24) is faulted. This
requires connecting D8129 OctoRelays to Zonex
Bus 1. Refer to the address settings on the back of
the D7212GV3 Program Record Sheet (P/N:
F01U170810).
Point 128 is reserved for use other than
an actual point. Only the first 24 points
can have an associated relay. Relays are
not available for Points 25 to 40.
Do not use the Change Relays? function
to toggle relays reserved for special
functions. Special function relays are
Area and Panel Wide Relay functions as
well as relays assigned to CC## Enter
Key Relay and P## Relay Response
Type.
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
Points
P## Display as Device
Default:
Selection:
Yes
No
Use P## Display as Device to cause the keypad to
display CHECK DEVICE when a point is off-normal or
is acknowledged after going into alarm.
Use this function for devices with a dry
contact output that faults a point when
the device is in a trouble condition.
P## Local While Disarmed
Default:
Selection:
Yes
No
Transmission of Restoral Reports continues
if the alarm, trouble, or bypass (by Sked,
RPS, or Swinger bypass) condition occurred
when the area disarmed, and the point
restored.
Use this option to allow a Controlled point (P## Type
1, 2, 3), to report Alarms, Troubles, and Restoral
Reports only when the area is armed. This prompt
does not affect local annunciation.
No
Yes or No
Display CHECK DEVICE when this
point is off-normal.
Do not display CHECK DEVICE when
this point is off-normal.
Refer to the program record sheet
Yes or No
Suppress Alarm, Trouble and
Restoral* Reports from this point
while the area to which it is
assigned is disarmed.
Send event reports occurring from
this point while the area is disarmed.
EN | 86