Table 34: Cross Point Ranges Within Groups
Cross Point
Group
1
2
3
4
5
When any Cross Point detects an alarm condition,
the control panel starts a timer as programmed in the
Cross Point Time prompt.
If a second Cross Point within the same Cross Point
Group detects an alarm condition, the control panel
creates a Cross Point Alarm Event for both points,
provided both points activate inside the Cross Point
Window.
If a single Cross Point detects an alarm and stays
faulted throughout the duration of the Cross Point
Window, a standard Alarm Report is generated for
that point.
Conversely, if a single Cross Point detects an alarm,
then restores, and no other conditions occur, an
Unverified Event is generated for that point. A second
alarm on the first point does not create an Alarm
Event but rather an Unverified Event.
Section 2.3 Routing on page 12 determines whether
these events are transmitted to a central station. An
Unverified Event does not produce a corresponding
Restoral Event.
The Cross Point function applies only to alarm
conditions. It does not apply to supervisory or trouble
conditions. Points programmed with point response D
(Delayed) eventually enter into an alarm condition if
the area is not disarmed in time.
Use the Cross Point function on Non-fire
points only.
Cross Point Time
Default:
20 sec
Selection:
5 sec to 255 sec
Select the amount of time (in seconds) that points
within a Cross Point Group are in alarm before a
Cross Point event is generated.
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
AUXPARM
Point Range
1
to
8
9
to
16
17
to
24
25
to
32
33
to
40
EN | 127