7 Line Supply Connection
7.3 Overcurrent protective devices, transformers and main switch
7.3.2

Assigning autotransformers to the I/R modules

Table 7-8
Autotransformers for 480/440 V input voltage
Nominal power rating [kVA]
S
Autotransf. IP00/IP20
S
Autotransformer IP23
Input voltage [V]
Output voltage [V]
Vector group
Permiss. ambient temperature
S
Operation
[_C]
S
Storage/transport
[_C]
Humidity classification in
accordance with
DIN EN 60721–3–3
Degree of protection acc. to
DIN EN 60529 (IEC 60529)
IP00/IP20/IP23
Order No.
mdexx GmbH
Richard–Dunkel_Straße 120
28199 Bremen
Germany
Tel.: +49 421 51 25 - 0
E-Mail: info@mdexx.de
Power loss [W]
S
Autotransf. IP00/IP20
S
Autotransformer IP23
Short–circuit voltage uk [%]
Conn. cross–section, max.
primary/secondary side
Fuse, primary side
Weight [kg], approx. for
S
Degree of prot. IP 00
S
Degree of prot. IP 20/23
7-220
Note
If, for I/R modules, a transformer is used, this does not replace the external
commutating reactor.
When using a transformer, from NE module  10 kW onwards,
Order No.: 6SN114V–1VV0V–0VV1), an overvoltage limiter module must be
used (Order No.: 6SN1111–0AB00–0AA0).
I/RF module
I/RF module
16/21 kW
36/47 kW
21
46.5
18.9
42
3–ph. 480/440 V AC $ 10%; 50 Hz – 10% to 60 Hz + 10%
3–ph. 400 V AC
Yna0;
neutral point N can be loaded only with maximum 10% if not corrected with an N (=
MP) line supply!
–25 to +40, for power derating up to +55 _C
–25 to +80
Class 3K5, moisture condensation and formation of ice not permissible
Low air temperature 0 _C
S
Degree of protection IP 00: V ––> Order No. A
S
Degree of protection IP 23: V ––> Order No. C
4AP2796–
4AU3696–
0EL40–2XV0
0ER20–2XV0
1)
160
430
135
370
v 3
2
2
16 mm
35 mm
35 A gL
80 A gL
29
52
40
70
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
I/RF module
I/RF module
55/71 kW
80/104 kW
70.3
104
63.3
93.5
2)
4AU3696–
4AU3996–
2NA00–2XV0
0EQ80–2XV0
550
700
460
590
2
70 mm
Flat termination
125 A gL
160 A gL
66
95
85
115
© Siemens AG 2012 All Rights Reserved
05.08
02.12
05.01
I/RF module
120/156 kW
155
140
IP00: 4BU4395–
0CB50–8B
IP20: 4BU4395–
0CB58–8B
IP23: 4BU4395–
0CB52–8B
700
600
3)
224 A gL
135
155

Hide quick links: