8 Important Circuit Information
8.16 VPM Voltage Protection Module
Signal contact X3
!
!
8-330
When the VPM is tripped or in the event of a temperature fault, signaling contact
X3 opens and interrupts the pulse enable of the SIMODRIVE converter
(see Fig. 8-45).
Warning
The signaling contact X3 closes autonomously after t > 2 min or after the
temperature switch has been reset. Therefore, measures must be adopted to
prevent the drive from starting by itself!
u2 min
Fig. 8-45
Signaling contact X3 of the VPM
Table 8-7
Technical data, signaling contact X3
Designation
Contact
1.Operating message
2. Operating voltage +24 V (from external)
Switch rating
Switching voltage/switching current
Interrupts when the housing temperature
Switches back
Interruption time after the start of short–cir-
cuit operation
Terminal type:
Spring loaded terminal WAGO, type 226–111, cable cross–sectionmax.: 1,5 mm
ded cable
Cable gland: max. 9 mm ∅.
Types VPM 120, VPM 200 and VPM 200 Dynamik
S
Screwed connection: 1 x M16, z. B. Fa. Pflitsch, Order No.: UNI DICHT
EMV 2165211S05
S
counter nut: M16: GM216PA.
Caution
When a VPM is tripped, the short–circuit thyristor must be safely cleared before
the connected drive can be switched on again. This is only ensured if the motor
has first come to a standstill.
An X3 signal contact that has closed again is not an explicit indication that
this has occurred.
Be especially cautious of this in the event of servicing.
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
X3
ϑ
w 60 _C
off
ϑ
ϑ
v 55 _C
on
Technical specifications
NC contact, floating
30 V DC at 0.1 A
min 19 V/10 mA
w80 $2.5 _C
v55 _C
u2 min
Note:
This value is valid 15 s after the drive and
pulse enable
© Siemens AG 2012 All Rights Reserved
02.07
05.01
2
,shiel-