Allen-Bradley 1398 ULTRA Plus Series Installation Manual page 36

Positioning drive module
Table of Contents

Advertisement

2-18
Install the ULTRA Plus PDM Components
At terminal block,
remove jumper
installed at factory
for internal shunt
1
2
3
TB2
WARNING: High Voltage
May Exist Up To Five Minutes
After Removing Power
DC Bus
R
S
T
DC Bus +
DC Bus -
L1
L2/N
L3
L1 AUX
L2/N AUX
T 1
B
Publication 1398-5.1 — January 2000
Figure 2.12
External Shunt (900W) mounting and connection diagram
Cabinet
STATUS
A1
A2
COM
"
+
J5
J4
J3
se twisted conductors
(2 twists per foot)
minimum or a shielded
J2
twisted pair
8 AWG (8.4 mm)
105 °C, 600V wire
J1
Max. Length 3.05 m
(10 ft) for each wire
There must be 155mm (6.1 in.) Of
clearance on all sides of
shunt module
Connect wires
to terminal block
inside front cover
There must be
155mm (6.1 in.)
of clearance on
all sides of
shunt module

Advertisement

Table of Contents
loading