3 PHASE TRANSFORMER SECONDARY VOLTAGE
AND CORRESPONDING DC BUS VOLTAGE,
VERSUS DC BUS CURRENT
FOR 3, 6, 12, AND 18 kVA TRANSFORMERS
330
320
310
300
290
280
270
260
3 kVA
250
0
10
20
30
40
BUS CURRENT (ADC)
Figure 2.2
Three PhaseTransformer Load Regulation Curves
233
226
219
212
12/18 kVA
205
198
191
6 kVA
184
177
100
50
60
70
80
90
1
D
B-C B-19866,C-19960
A
REV ECO
DO NOT SCALE DRAWING
DIMENSIONS ARE IN INCHES
BREAK ALL EDGES .02 MAX
FILLETS AND ROUNDS .02 R MAX
TOLERANCE ON:
ANGLES ±1ANGLES ˚
FRACTIONS:±1/64"
DECIMALS.XX±.020
NOTES:
1
DC BUS VOLTAGE AND CURRENT IS MEASURED AT POS & NEG
OUTPUT TERMINALS OF THE POWER SUPPLY MODULE.
2. CURVES SHOW REDUCTION IN TRANSFORMER SECONDARY VOLTAGE
AND THE DRIVE MODULE DC BUS VOLTAGE, DUE TO TRANSFORMER
INTERNAL LOSSES, AS BUS CURRENT LOAD INCREASES.
3. ALL DATA TAKEN WITH TRANSFORMER PRIMARY VOLTAGE HELD
TO 480 VAC 3 PHASE LINE TO LINE 60 Hz AND WITH SECONDARY
WIRED FOR 230 VAC LINE TO LINE NO LOAD.
JL
20625
UPDATE TITLE BLOCK
BC
16383
RELEASED
BY
REVISION DESCRIPTION
UNLESS OTHERWISE SPECIFIED
.XXX±.010
Install the ULTRA Plus PDM Components
RELIANCE MOTION CONTROL
3 PHASE TRANSFORMERS
PART NUMBER
kVA
0020-5091-001
3
0020-5091-002
6
0020-5091-003
12
0020-5091-004
18
8-5-88
DATE
DRAWN BY
DATE
DESIGN ENGR
BC
8-5-88
JH
DIAG, XFMR LOAD REG
PART NO.
9101-0132
SCALE
DWG SIZE
1:1
Publication 1398-5.1 — January 2000
2-7
__
__
JH
CHKR
DATE
8-5-88
SHEET
A
1
1
of

Advertisement