Tune Mode Configuration Procedures - Partlow MIC 8200 Installation And Operation Manual

Process controller
Table of Contents

Advertisement

TABLE 3-3 TUNE MODE CONFIGURATION PROCEDURE
Depress and release the SCROLL key until tunE is displayed. Use the DOWN key to enter
the Tune mode. Depress and release the SCROLL key to sequence through the parameters
and their values.
The upper display will be the parameter code, the lower display will
indicate the parameter value selected. Use the UP and DOWN keys to adjust the values.
After adjusting a parameter, depress the SCROLL key to proceed to the next parameter. Use
the DOWN key to advance to the next parameter code when a parameter code is showing in
the upper display and the lower display is blank. After all selections have been made,
depress the UP key with a parameter code showing in the upper display and the lower display
blank, to exit the mode.
STEP
DESCRIPION
1
Process Alarm
(PAL will be seen
if out3=1 or 2)
2
Deviation Alarm
(dAL will be seen
if out3=3 or 4)
3
Deviation Band
Alarm
(dbAL will be seen
if out3=5 or 6)
4
1st Output
Proportional
Band Width
(Pb1 will not be
seen if out1=1,2)
5
2nd Output
Proportional
Band Width
(Pb2 will not be
seen if out2=0,1,2,7)
6
Manual Reset
7
Automatic Reset
Output 1 (Integral)
8
Automatic Reset
Output 2 (Derivative)
9
Rate (Derivative)
Output 1
10
Rate (Derivative)
11
Cycle Time
Output 1
(Ct1 will be seen if
out1=3,4,7)
12
Cycle Time
Output 2
(Ct2 will be seen
if out2=3 or 4)
(Continued on next page)
DISPLAY
AVAILABLE
CODE
SETTINGS
-9999 to 9999 °/units
PAL
-3000 to 3000 °/units
dAL
dbAL
1 to 3000°/units
Pb1
1 to 3000°/units
Pb2
1 to 3000°/units
rSt
-1500 to 1500°/units
ArS1
0.0 to 100.0 repeats
per minute
ArS2*
0.0 to 100.0 repeats
per mintue
rt1
0.0 to 10.0 minutes
rt2*
0.0 to 10.0 minutes
Ct1
1 to 240 seconds
Ct2
1 to 240 seconds
FACTORY
YOUR
SETTING
SETTING
0
0
1
100
100
0
0.0
0.0
0.0
0.0
30
30
P
35
AGE