Wiring Label - Partlow MIC 8200 Installation And Operation Manual

Process controller
Table of Contents

Advertisement

P
12
AGE
(Continued from page 11)
Example:
An application uses 2000 feet of 18 AWG copper lead wire for a 3 wire RTD sensor. What is
the worst case error due to this leadwire length?
Terr = TLe * L
TLe = +/-.46 (°F/1000 ft) from Table 3
Terr = +/-.46 (°F/1000 ft) * 2000 ft
Terr = +/- 0.92°F
FIGURE 2-4 WIRING LABEL
H
RELAY C
G
F
RELAY B
E
D
RELAY A
C
B
115
VAC
230
A
SERIAL A
SERIAL B
INPUT RATINGS:
115/230 VAC 50/60 HZ 15VA MAX
RELAY OUTPUT RATINGS:
115VAC 5.0A RESISTIVE
230VAC 2.5A RESISTIVE
230VAC 1/8 HP
115/230VAC 250VA
MAXIMUM AMBIENT : 55°C
GROUND
POS.PROP.
REMOTE
8
WIPER
SETPT
POS.PROP.
OUT2
7
HIGH
4-20mA
OUT1
4-20mA +
6
RETURN
5
CJC
4
3
SIGNAL +
CJC
2
1
SIGNAL -
MADE IN U.S.A
+
+