Partlow MIC 8200 Installation And Operation Manual page 32

Process controller
Table of Contents

Advertisement

P
32
AGE
* Factory setting for Total
Access
STEP
DESCRIPION
28
Process Rounding Prnd
29
Current Output 1
Range
30
Current Output 2
Range
31
Process Output
32
Process Output
Upper Value
(Pou and PoL will
not be seen if
Pout=0)
33
Process Output
Lower Value
34
Proportional
Output 1 Action
on Error Condition
(P1EC will not be
seen if out1=1,2)
35
Proportional
Output 2 Action
on Error Condition
(P2EC will not be
seen if out2=0,1,2,7)
36
Setpoint
Ramp Rate
(Cannot be used
in conjunction with
Auto Tune)
Communication Parameters 37-39 are optional and will only be displayed on models 82XXX3X, 82XXX4X,
82XXX5X or 82XXX6X
37
Communications
Configuration
38
Communications
Bit Rate
39
Communications
Address
DISPLAY
AVAILABLE
CODE
SETTINGS
1 to 100 degrees/units
1 = no rounding
Co1r
0 = 0 to 20mADC
1 = 4 to 20mADC
Co2r
0 = 0 to 20mADC
1 = 4 to 20mADC
Pout
0 = Not selected
1 = Assigned to
2 = Assigned to
Pou
-9999 to 9999 degrees/units 2000
PoL
-9999 to 9999 degrees/units 0
P1EC
0 - 100%
P2EC
0 - 100%
SPrr
0 to 100°/Units per minute
0 = not used
CCon
0 = Off
1 = Monitor (Read Only)
2 = Full Communications
CbS
1 = 300 bit rate
2 = 600 bit rate
3 = 1200 bit rate
4 = 2400 bit rate
5 = 4800 bit rate
6 = 9600 bit rate
CAd
0 to 99
FACTORY
YOUR
SETTING
1
1
1
0
Current Output 1
Current Output 2
0
0
0.0
0, 4*
(Read & Write)
6
0, 1*
SETTING

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents