TABLE 3-2 PROGRAM MODE CONFIGURATION PROCEDURE
Press and release the SCROLL key until Prog is displayed. Use the DOWN key to enter the
Program mode. Depress and release the SCROLL key to advance the display through the
parameters and their values. The upper display will show the parameter codes. The lower
display will show the parameter value selected. Use the UP and DOWN keys to adjust the
parameter values. After adjusting a parameter, depress the SCROLL key to proceed to the
next parameter. After all selections have been made, depress the UP key with a parameter
code in the upper display and the lower display blank to exit the mode.
Note that parameter values are referred to in Degrees (°) and Engineering Units in the following tables. The input
selection determines what the parameter values will be.
STEP
DESCRIPTION
1
Input Select
2
Input Correction
3
Output 1
4
Output 1 %
Upper Limit
(o1uL and o1LL will
be displayed if out1 is not
selected as 1 or 2)
5
Output 1 %
Lower Limit
DISPLAY
AVAILABLE
CODE
SETTINGS
0 = J °C
inPS
1 = J °F
2 = K °C
3 = K °F
4 = T °C
5 = T ° F
6 = R °C
7 = R °F
8 = S °C
9 = S °F
10 = E °C
11 = E °F
12 = B °C
13 = B °F
14 = N °C
15 = N °F
16 = C °C
17 = C °F
20 = RTD °C
21 = RTD °F
30 = 0 - 5VDC / 0 to 20mA
31 = 1 - 5VDC / 4 to 20mA
32 = 0 - 50mVDC
33 = 10 - 50mVDC
34 = 0 - 25mVDC
iCor
-300° to 300°/Units
out1
1 = On-Off Direct (Cooling)
2 = On-Off Reverse (Heating)
3 = Time Proportioning -
4 = Time Proportioning -
5 = Current Proportioning -
6 = Current proportioning -
7 = Position Proportioning -
o1uL
1 to 100%
o1LL
0 to 100%
FACTORY YOUR
SETTING SETTING
1
Thermocouple
0
2
Direct (Cooling)
Reverse (Heating)
Direct (Cooling)
Reverse (Heating)
Open
100
0