Partlow MIC 8200 Installation And Operation Manual page 59

Process controller
Table of Contents

Advertisement

FbEr
Slidewire Feedback Error
Hi - Input more than 10%
Over Span
Lo - Input more than 10%
Under Span
o - display overrange
(the "broken 6" appears
on the left side of the display)
Er 1 - Microprocessor RAM
Failure
Er 2 - External RAM Failure
Er 3 - EPROM Checksum
Failure
Er 4 - RTD Mismatch Error
Er 5 - No Zero Crossings
Detected
1. Inspect the Slidewire Feedback connections at
terminals 8, 7, and 5. Be sure that the
connections are the same as shown in the position
proportioning illustration (page 20).
2. Measure the resistance of the Slidewire segment.
The minimum resistance must be 135 ohms, the
maximum 10 K ohms.
3. Perform the Auxiliary Input Test. Test 9 as
described in the Test section, (page 55) the
voltage indicated should be between 0 and 5 VDC.
4. Turn off the power to the instrument. Loosen the
front panel screw and take the instrument out of
the housing. Verify that the jumper JU-1 on the
Option Board (Appendix A-3, page 66 and 67)
is in the Motor Modulation position.
1. Perform the steps listed for the SnSr error
condition (page 58).
1. Perform the steps listed for the SnSr error
condition (page 58).
1. If this error code is displayed as a Program or Tune
mode parameter value , perform the Cal 1
procedure as described in the Calibration
section (page 48).
2. If this error code appears as part of the model
number during the power up sequence, follow the
steps listed for the "Model number incorrect"
condition (page 56).
1. Turn off the power to the instrument.
2. Loosen the front panel screw and remove the
instrument from the housing. Inspect that the
microprocessor (U1) is properly seated in the socket
located on the Processor board (Appendix A-2, page
65). Return the instrument to the housing and
tighten the front panel screw. Turn on the power.
1. Turn off the power to the instrument. Wait 5
seconds, and turn the power on.
1. Perform the steps listed for Er 1 except that the
EPROM (U2) on the Processor board should be
inspected.
1. Check the connections to the instrument for the
RTD Input Calibration CAL5 as described in the
Calibration section (page 51). Repeat the RTD
Input Calibration.
1. Turn off the power to the instrument. Wait 5
seconds and turn the power on.
2. Turn off the instrument power. Loosen the front
panel screw and remove the instrument from the
housing. Inspect the white ribbon cable that connects
the Processor board to the Power Supply board. Be
sure that the cable is properly aligned and seated in
socket on the Power Supply board. Return the
instrument to the housing and tighten the front panel
screw. Turn on the power to the instrument.
3. Connect the instrument to another AC power source.