Remote Setpoint Input - Partlow MIC 8200 Installation And Operation Manual

Process controller
Table of Contents

Advertisement

P
16
AGE
FIGURE 2-10
Remote Setpoint Input - VDC and mADC and Potentiometer
Input connections are illustrated below. Terminal 8 is positive and terminal 5 is negative.
The remote setpoint input can be configured for either 0 to 5VDC or 1 to 5 VDC input. Make
sure that the voltage input matches the voltage configuration selected in the Program mode.
For mA inputs, a 250 ohm shunt resistor must be installed between terminals 5 and 8. For
remote setpoint using a potentiometer, JU1 on options board must be in MM/PP (see page 66
and 67).
CURRENT DC REMOTE SETPOINT
Rear View
+
8
7
6
-
5
4
3
2
1
Shielded Twisted Pair
MILLIAMP
SETPOINT
SIGNAL
250 OHM
SHUNT
RESISTER
NEEDED
POTENTIOMETER
Rear View
8
7
6
5
4
3
2
1
VOLT DC REMOTE SETPOINT
Rear View
+
8
7
6
-
5
4
3
2
1
150 ohm to
10 K ohm
Shielded Twisted
Pair
VOLT DC
SETPOINT
SIGNAL
5VDC
MAXIMUM