Partlow MIC 8200 Installation And Operation Manual page 33

Process controller
Table of Contents

Advertisement

STEP
DESCRIPION
40
Auto Tune
Deviation
Upper Limit
40
Auto Tune
Deviation
Lower Limit
40
Auto Tune Setpoint ASuL
Upper Limit
41
Auto Tune Setpoint ASLL
Lower Limit
42
Control Response CrC
Criteria
43
Control Algorithm
44
Auto Tune
Abort Option
45
Auto Tune
Time Limit
46
Auto Tune Select
Option for On Demand
* Whenever inPS is changed, the parameter is set to the upper limit of advertised
specifications section (Appendix D, page 74)
DISPLAY
AVAILABLE
CODE
SETTINGS
AduL
0° to 1000°
AdLL
0 to 5000°
0 = no lower limit
-9999° to 9999°
-9999° to 9999°
1.0 to 2.0
1.0 = 1/4 Amplitude Decay
2.0 = Damped Response
CAC
1 = PID
2 = PI
3 = P
AAo
0 = Go into Standby at
1 = Go into Standby at
2 = Go into Control with last
3 = Go into control with PID
parameters of ArS1 = 0,
rt1 = 0 and
a) if dPoS = 0, Pb1 = 100
b) if dPoS = 1, Pb1 = 10
AtL
0 = No Limit
1 to 500 minutes
ASo
0 = On demand not selected 0
1 = On demand selected
FACTORY
YOUR
SETTING
0
0
1400*
0
2.0
Response
2
0
0% output
o1LL % output
PID parameters
0
span as indicated in the
SETTING
P
33
AGE