Tune Mode Configuration Procedures - Partlow MIC 2000 Installation And Operation Manual

Table of Contents

Advertisement

TABLE 3-3 TUNE MODE CONFIGURATION PROCEDURE
Depress the SCROLL key until tunE is displayed. Use the DOWN key to enter the Tune
mode. Depress and release the SCROLL key to sequence through the parameters and their
values. Use the UP and DOWN keys to adjust the values. After adjusting a
parameter, depress the SCROLL key to proceed to the next parameter. After all
selections have been made, depress the UP key with a parameter code displayed (not a
setting) to exit the mode.
S T E P
DESCRIPTION
1
Spread (Second SPrd
Output Position)
2
Process Alarm
3
Deviation Alarm
4
Deviation Band
Alarm
5
1st Output
Proportional
Band Width
6
2nd Output
Proportional
Band Width
7
Manual Reset
8
Automatic Reset ArSt
(Integral)
9
Rate ( Derivative) rAtE
10
Cycle Time
Output 1
11
Cycle Time
Output 2
12
Position Prop.
Sensitivity
13
First Output
Position
Note: The Program, Tune and Enable Mode selections can be conveniently recorded on
the Software Reference Sheet located in Appendix E (page 70).
DISPLAY
AVAILABLE
CODE
SETTINGS
-1000 to 1000 °/units
-9999 to 9999 °/units
PAL
-3000 to 3000 °/units
dAL
1 to 3000 °/units
dbAL
1 to 3000 °/units
Pb1
1 to 3000 °/units
Pb2
-1500 to 1500 °/units
rSEt
0.0 to 100.0 repeats
per minute
0.0 to 10.0 minutes
Ct1
1 to 240 seconds
Ct2
1 to 240 seconds
SEnS
0.0 to 50.0 %
-1000 to 1000 °/units
FoP
FACTORY
YOUR
SETTING
SETTING
0
0
0
1
100
100
0
0.0
0.0
30
30
1.0
0
P
33
AGE

Advertisement