TESTO 6681 Instruction Manual page 30

Humidity transmitter with ethernet module
Hide thumbs Also See for 6681:
Table of Contents

Advertisement

testo 6681 Ethernet
30
Connection note
- 1.3 Commissioning
For the connection, a double-insulated mains cable
(sheathed cable) with a cross-section of at least 1.5 sq.
mm must be used.
Cable connection (2) may not be routed in a loop within
the tray (1).
In order to protect from electrical shock if the wire severs
or falls out, 3 wires must always be bound together with a
cable tie (3).
The insulation of the cable must be fed at least 5 mm (4)
into the tray.