Alarm Handling - TESTO 6681 Instruction Manual

Humidity transmitter with ethernet module
Hide thumbs Also See for 6681:
Table of Contents

Advertisement

testo 6681 Ethernet
18
Parameter
Water content
Water vapour partial pressure

1.2.9 Alarm handling

For upper and lower alarm limits, individual alarms as well as collective
alarms can be specified. If the collective alarm function is activated, an alarm
is triggered as soon as the alarm limit of an alarm is exceeded, if this alarm is
assigned to the collective alarm.
The testo 6681 monitors limit values using relays. If a reading is outside the
limit values, a relay to be specified by the user is switched.
If the reading reverts to more than a specified hysteresis below or above the
limit value, the alarm is cancelled.
In addition, information about the occurrence of error/status messages can
be provided by means of a collective alarm relay, see chapter 1.5, Status,
warning and error messages, page 87.
- 1.2 Product description
Unit
ppm vol
H2O
% vol
hPa
inchH2O
If multiple alarm messages are activated at the same time,
the last alarm is shown. If the alarm is cancelled again, the
previous messages are no longer shown.
Example:
If the condensation of the probe begins, the "Condensation"
message appears on the display and the "Start" status
display. If the condensation is over, the status display
changes from "Start" to "End".
Probe
at 1013 hPa
MIN
Standard
scaling
Measuring
MUF
range
measuring
Physical
range
MAX
MIN MAX
0
99999
0
100
0
1000
0
400
0 99999
0
100
0
7000
0
2800