Handling

2.1

Installation

2.1.1

Mounting location

Boiler control panel
In the control panel front
2.1.2

Regulations for installation

A clearance of at least 10 mm must be provided on all sides of the controller,
enabling the unit to emit the amount of heat produced during its operation. The
space should not be accessible and no objects should be placed there.
The controller is designed for mounting in a boiler control panel. Power to the
controller may be supplied only after it is completely fitted in the cutout. If this is not
observed, there is a risk of electric shock near the terminals and through the
cooling slots.
If the controller shall be mounted directly on the wall, a housing must be used to
provide protection against electric shock hazard. The housing must have a
sufficient number of cooling slots at the bottom and the top, allowing the controller
to emit the heat it produces.
The controller has been designed based on the guidelines of safety class 2 and
must therefore be mounted in compliance with these regulations.
The controller may not be exposed to dripping water.
Permissible ambient temperature:
2.1.3

Mounting procedure

Description
Turn off power supply
Pull the prefabricated cables
through the cut-out
Plug the connectors into the
respective sockets at the rear of the
controller
Note:
The connectors are coded to make
certain they cannot be mixed up.
Basic Documentation RVA47.320
Handling
0...50 °C
Diagram
2379Z11
13/166
CE1P2379E
15.07.2002