Configuration of plant

6.9

Continuous display

Selection of value for the continuous display.
Determines to kind of information to appear on the continuous display.
1.
Press the line selection buttons to select operating line 90
2.
Press the + / - buttons to select the required continuous display.
Setting range
0 / 1
This setting changes the continuous display of the device. It appears when no
operating line is selected.
0
Day / time of day
The continuous display shows the weekday (1...7 = Mo...Su) and the time of
day.
1
Cascade flow temperature sensor (common flow temperature sensor)
The continuous display shows the temperature measured with the cascade flow
temperature sensor (B10)
When connecting several BMUs to the controller, the continuous display always shows
the cascade flow temperature. In that case, setting 0 can be no longer selected.
8
12
16
0
4
Basic Documentation RVA47.320
Description of the OEM settings
Unit
-
20
24
.
OEM
Factory setting
0
CE1P2379E
15.07.2002