7.5

D.h.w. push

Availability of d.h.w. is also ensured during non-occupancy times.
If, due to unexpected demand, the d.h.w. storage tank is emptied, the d.h.w. push
provides one-time charging of the storage tank until the nominal d.h.w. temperature
setpoint is reached.
The d.h.w. push is triggered as soon as the actual d.h.w. temperature falls below the
reduced d.h.w. setpoint (line 120) by more than twice the switching differential (line
41
).
OEM
TBWx < TBWR - 2 SDBW
When the d.h.w. push is triggered, the storage tank is charged once until the nominal
d.h.w. temperature setpoint (operating line 13) is reached.
Then, normal operation according to the d.h.w. heating program is resumed.
TBWw
SDBW
TBWR
TBWw
TBWR
SDBW
Switching differential d.h.w.
TBWw
Nominal d.h.w. temperature setpoint
TBWR
Reduced setpoint of the d.h.w. temperature
Basic Documentation RVA47.320
Functions with no settings
TBWx
Push
SDBW
·
2
SDBW
t
CE1P2379E
15.07.2002