Function
171
minimum setpoint of flow temperature contact H1
If activated at input H1 (setting 2)
172
Maximum value of heat demand
If activated at input H1 (setting 4)
173
operating action of the contact H1
0
N.C. contact
1
N.O.
26/166
Siemens Building Technologies
HVAC Products
1)
If a BMU is connected via LPB, this setting will not be active.
The respective setting must be made directly on the BMU.
Basic Documentation RVA47.320
Handling
Range
Unit
8...TKmax
°C
5...130
°C
0 / 1
-
Resolution
Factory
setting
1
70
1
100
1
1
CE1P2379E