Parameter Settings For The Oem - Siemens RVA47.320 User Manual

Cascade controller for modulating gas-fired boilers
Table of Contents

Advertisement

Description
Setting
Example
Siemens Building Technologies
HVAC Products
2.6

Parameter settings for the OEM

Boiler-specific settings and protective functions for the boiler manufacturer.
Buttons
Explanation
Press one of the line selection buttons.
1
This will take you first to the programming level
"Enduser".
Press both line selection buttons for at least 9 seconds.
2
A special display for entering the code will appear.
9 s
Press buttons
3
CODE
combination of the access code.
If the combination of buttons is correct, you reach the
programming mode "OEM".
If the code has been entered incorrectly, the display will
change to the "Parameter settings for the heating
engineer".
Press the line selection buttons to select the required
4
line.
The parameter list on the next 2 pages contains all
available lines.
Press the + or - button to set the required value.
5
The setting will be stored as soon as you leave the
programming mode or change to another line.
The following parameter list contains all available lines.
You leave the programming level "OEM" by pressing any
6
of the operating mode buttons.
If no button is pressed for about 8 minutes, the controller
will automatically return to the operating mode selected
last.
8
12
0
4
Whether correct or incorrect, each push of a button represents irrevocably a digit of the
code.
As a confirmation, the respective digit changes to 1.
Basic Documentation RVA47.320
Handling
and
Wrong code:
Note:
16
20
24
to enter the required
Line
• • •
Contin.
display
27/166
CE1P2379E
15.07.2002