Siemens RVA47.320 User Manual page 25

Cascade controller for modulating gas-fired boilers
Table of Contents

Advertisement

Line
Function
124
D.h.w. charging
0
Once per day (forward shift 2.5 h)
1
Several times per day (forward shift 1h)
125
Type of d.h.w. demand
0
Sensor
1
Control thermostat
126
Flow temperature boost for d.h.w.
127
d.h.w. priority
0
MK + PK absolute
1
MK + PK shifting
2
None (parallel)
3
MK shifting, PK absolute
129
demand for heat with reduced d.h.w. setpoint
0
No (application with buffer storage tank)
1
Yes
Boiler cascade
130
changeover of boiler sequence in cascades
---
No automatic changeover (fixed boiler sequence)
10...990
Changeover according to the selected number of hours
131
Exclusion with autom. changeover of boiler
sequence
0
None
1
First boiler
2
Last boiler
3
First and last boiler
132
Lead boiler with the fixed sequence
133
Switch-on delay lag boilers
134
Restart lock of BMUs
LPB / system
140
LPB device address
0
Standalone
1...16 Device number
141
LPB segment address
0
Central segment (heat generation)
1...14 Segment (heat consumers)
142
LPB power supply
0
Off (central bus power supply)
1
AUTOMATIC (controller - bus power supply)
143
Displaying the LPB power supply
144
displaying the LPB communication
Range of action of central changeover
145
0
In the segment
1
In the system (if segment address = 0)
146
Automatic summer / winter changeover
0
Effect on local heating circuit only
1
Central changeover of all heating circuits
147
Central standby switch
0
OFF (Inactive)
1
ON
(all units on standby)
148
clock mode
0
Autonomous clock
1
System time without remote adjustment
2
system time with remote adjustment
3
System clock (master)
149
Winter- / summertime changeover
150
Summer- / wintertime changeover
input H1
170
input H1
0
Changeover of operating mode (HC standby / d.h.w. off)
1
Changeover of operating mode (HC standby)
2
Minimum setpoint of flow temperature (setting on line 171)
3
Heat generation lock
4
Heat demand DC 0...10 V
Siemens Building Technologies
HVAC Products
Basic Documentation RVA47.320
Handling
Range
Unit
0 / 1
-
0 / 1
-
0...30
K
0...3
1
0 / 1
-
--- / 10...990
- / hours
0...3
-
00.1...16.3
-
2...120
min
0...1800
s
0...16
-
0...14
-
0 / 1
-
ON / OFF
-
ON / OFF
-
0 / 1
-
0 / 1
-
0 / 1
-
0...3
-
01.01...31.12
tt.MM
01.01...31.12
tt.MM
0...4
-
Resolution
Factory
setting
1
1
1
0
1
16
1
1
1
1
10
500
1
0
01.1
-
1
5
10
300
1
1
1
0
1
1
-
-
-
-
1
1
1
0
1
0
1
3
1
25.03
1
25.10
1
0
25/166
CE1P2379E
15.07.2002