Benefit
Description
Setting
32/166
Siemens Building Technologies
HVAC Products
3
Description of the enduser settings
User interface
3.1
Heating circuit operating modes
•
Straightforward selection of heating circuit operating modes
The control provides 3 different heating circuit operating modes that can be directly
selected as required.
Select the required operating mode by pressing the respective operating mode button.
It is located on the controller front for direct access by the user.
Operating
Designation
mode
Automatic
operation
continuous
operation
Standby
Basic Documentation RVA47.320
Description of the enduser settings
Effect of selected operating mode
•
Heating according to the time program
(operating lines 5 to 11)
•
Temperature setpoints according to the heating
program
•
Protective functions active
•
Changeover on the room unit active
•
Automatic summer / winter changeover and
automatic 24-hour heating limit active (ECO
functions)
•
Heating mode with no time program
•
Temperature adjustment with the setpoint knob
•
Protective functions active
•
Changeover on room unit inactive
•
Automatic summer / winter changeover and
automatic 24-hour heating limit inactive (ECO
functions)
•
Heating OFF
•
Temperature according to frost protection
•
Protective functions active
•
Changeover on room unit inactive
CE1P2379E
15.07.2002