Plant Types Rva47.320 - No. 65 - Siemens RVA47.320 User Manual

Cascade controller for modulating gas-fired boilers
Table of Contents

Advertisement

Note
Hydraulic circuit
Type of unit
Display of plant type
Heating curve (line 17)
Pump function Q1 (line 95)
Important
Electrical connections
Legend
Siemens Building Technologies
HVAC Products
8.5
Plant types RVA47.320 - no. 31
The plant type no. is identical with the number displayed on line 53.
Control of a single BMU or cascade control of up to four BMUs. D.h.w. heating with
charging pump through the RVA47.320.
System pump for heating circuits and d.h.w. heating connected to RVA47.320.
1
BMU 1
BMU 2
Heat generation is released by the heat demand signal from a consumer (or d.h.w.
heating):
LPB capable controllers signal the RVA47.320 their current heat demand directly
via LPB.
• Controllers not suited for use with the LPB can deliver their heat demand signal via
input H1.
When there is no heat demand signal from the consumers (no LPB capable controllers
connected and no possibility to use input H1), the controller itself can generate a
weather-compensated flow temperature (adjustment of heating curve with a valid
value).
H1
B3
B70
M
B
M
B
M
B
B3
H1
B7
Q3
Q1
F1
N
L
For a detailed legend, refer to page 158.
Basic Documentation RVA47.320
Application examples
2
3
BMU 3
BMU 4
A6 / BMU
B10
B9
M
B
M
B
PPS
MD
M
B10
B9
A6
N1
L
B10
4
B70
RVA47.320
31
--- (inactiv) or 2.5...40
3 (primary pump for HC and d.h.w.)
LPB
MB
DB
N
B3
149/166
CE1P2379E
15.07.2002