Heating Circuit Values; Parallel Displacement Of The Heating Curve; Room Influence - Siemens RVA47.320 User Manual

Cascade controller for modulating gas-fired boilers
Table of Contents

Advertisement

Benefit
Description
Setting
Effect
Example:
Parallel displacement
Benefit
76/166
Siemens Building Technologies
HVAC Products

Heating circuit values

4.27

Parallel displacement of the heating curve

Adjustment of controller's temperature scale to the actual plant conditions.
Produces a parallel displacement of the heating curve in order to achieve a better
match of room temperature setpoints and actual room temperatures.
1. Press the operating line selection buttons to select operating line 100.
2. Press the + / – buttons to set the parallel displacement..
Setting range
-4.5...+4.5
By changing the value entered, all room temperature setpoints will be appropriately
raised or lowered. This allows the room temperature setpoints to be matched to the
effective room temperatures.
If a nominal room temperature setpoint of 20 °C adjusted on the controller always
produces a room temperature of 22 °C (independent of the prevailing outside
temperature), displace the heating curve downward by 2 °C.
Each setpoint readjustment, be it by changing the setting value or the operational level,
corresponds to a parallel displacement of the heating curve.
TV
°C
100
90
80
70
60
50
40
30
30
20
10
10
10
0
TV
Flow temperature
TA
Composite outside temperature
TRw
Room temperature setpoint
4.28

Room influence

More accurate room temperature control due to temperature checkback signal from
the space
Use of heat gains
Possibility of boost heating and quick setback
Basic Documentation RVA47.320
Description of the heating engineer settings
Unit
°C (K)
0
-10
-20
0
Factory setting
0.0
°C
-30
TA
CE1P2379E
15.07.2002