Actual values

Overview of the actual temperatures of the sensors used
Better reproducibility of the control sequences thanks to visualized temperatures
4.5
Actual boiler temperature values of BMUs
(TKx)
1.
Press the operating line selection buttons to select operating line 55.
2. Press the + / - buttons to interrogate the individual BMUs.
Display
1...4 / 0...140
The lowest connected BMU number with the associated temperature will automatically
be displayed on this line. The temperatures of the other cascaded heating boilers can
be interrogated by pressing the + / - buttons. Non-existing BMUs will be skipped.
The cascade boilers displayed are only those connected to this controller. If there are
additional cascaded boilers, they will be displayed on the controllers to which they are
physically connected.
In place of the temperature, the following displays can appear next to the BMU number:
– – –
Sensor with an open-circuit or no sensor connected
0 0 0
Sensor with short-circuit
If the LCD displays – – – without giving an associated BMU number, there is no BMU
connected to the controller.
4.6

Actual value of cascade flow temperature

When using several cascaded heat sources, a cascade flow temperature sensor (B10)
must be installed.
Also termed "Common flow temperature sensor".
1. Press the operating line selection buttons to select operating line 56.
2. No setting can be made with the + / - buttons.
Display
0...140
The temperature measured with the cascade flow temperature sensor (B10) will
automatically be displayed on this line.
In a cascaded system, a common cascade flow temperature sensor (B10) is used for
all heat sources.
The cascade temperature sensor (B10) is connected directly to the RVA47.320.
Basic Documentation RVA47.320
Description of the heating engineer settings
Unit
BMU number / °C
Unit
°C
CE1P2379E
15.07.2002