Note
Hydraulic circuit
Type of unit
Display of plant type
Heating curve (line 17)
Pump function Q1 (line 95)
Important
Electrical connections
Legend
150/166
Siemens Building Technologies
HVAC Products
8.6
Plant types RVA47.320 - no. 32
The plant type no. is identical with the number displayed on line 53.
Control of a single BMU or cascade control of up to four BMUs. D.h.w. heating with
charging pump through the RVA47.320.
Primary pump for heating circuits connected to the RVA47.320.
1
BMU 1
BMU 2
Heat generation is released by the heat demand signal from a consumer (or d.h.w.
heating):
LPB capable controllers signal the RVA47.320 their current heat demand directly
via LPB.
• Controllers not suited for use with the LPB can deliver their heat demand signal via
input H1.
When there is no heat demand signal from the consumers (no LPB capable controllers
connected and no possibility to use input H1), the controller itself can generate a
weather-compensated flow temperature (adjustment of heating curve with a valid
value).
H1
B70
B3
M
B
M
B
M
B
B3
H1
B7
Q3
Q1
F1
N
L
For a detailed legend, refer to page 158.
Basic Documentation RVA47.320
Application examples
2
3
BMU 3
BMU 4
A6 / BMU
B10
B9
M
B
M
B
PPS
B10
B9
MD
M
A6
N1
L
B10
B3
4
B70
RVA47.320
32
--- (inactiv) or 2.5...40
2 (primary pump for HCs only)
LPB
MB
DB
N
CE1P2379E
15.07.2002