Running Time Strategies - Siemens RVA47.320 User Manual

Cascade controller for modulating gas-fired boilers
Table of Contents

Advertisement

General
Notes
Important
Strategy 1:
Example of three boilers
with an output range of 20
- 80 %:
Siemens Building Technologies
HVAC Products
6.4.2

Running time strategies

The running time strategy defines the criteria for the switching on / off of the lag boilers.
It is determined by the following parameters:
- Nominal output of BMU 1 - 4
- Entry of minimum limit of output range (Pmin)
- Entry of maximum limit of output range (Pmax)
The RVA47.320 initiates changeover only when it leads to a valid operational status
while taking the above parameters into consideration.
The following parameters also have an impact on the function:
- Delayed switching on of BMU
- Restart lock for BMU
For stability reasons, each BMU added to the cascade first runs on the basic stage for
about one minute on completion of which it will be released for modulating control to
deliver the output required.
The running time strategies described below become active only when the flow
temperature setpoint is reached. During the heating up time (e.g. after night setback),
the boilers required are run up to the maximum released output as quickly as possible
(short heating up time).
Additional boilers are switched on as late as possible and switched off again as early as
possible. Hence, the aim is to have the smallest possible number of boilers in
operation, or to obtain short running times for additional boilers.
80%
ON
80%
40%
40%
53%
53%
80%
40%
40%
80%
OFF
= increase in output
= decrease in output
P
= OutputLeistung
Basic Documentation RVA47.320
Description of the OEM settings
see line 134
80%
ON
80%
80%
53%
53%
80%
80%
53%
53%
80%
OFF
= Switching onZuschaltung
= Switching offWegschaltung
See line 91 -94
See line 10
OEM
See line 52
OEM
see line 133
2379Z05a
80%
100%
100%
80%
129/166
CE1P2379E
15.07.2002
100%
P