Setting the clock ................46 Time of day ..................46 Weekday ..................46 Date (day, month) ................47 Year ....................47 Time switch program 1................ 48 3/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Contents 26.03.2001...
Page 4
Description of heating engineer settings..........72 Service values ..................72 Output test..................72 Input test ...................73 Display of plant type................74 Actual values..................75 Actual value of flow temperature (B1) ............75 4/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Contents 26.03.2001...
Page 5
Minimum limitation of flow temperature setpoint HK2 (TVmin) ....102 4.41 Maximum limitation of flow temperature setpoint HK1 (TVmax)....103 4.42 Maximum limitation of flow temperature setpoint (TVmax) HK2 ....103 5/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Contents 26.03.2001...
Page 6
Demand for heat with reduced d.h.w. setpoint........139 Multi-functional inputs................ 140 4.78 Input H1................... 140 4.79 Minimum flow temperature setpoint contact H (TVHw) ......144 6/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Contents 26.03.2001...
Page 7
Constant for quick setback and optimum start control (KON)....170 5.23.1 Quick setback without room influence..........171 5.23.2 Optimum start control without influence..........171 5.24 Boost of room temperature setpoint (DTRSA) ........172 7/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Contents 26.03.2001...
Page 8
D.h.w. push..................195 6.10 Pump and valve kick ................. 196 6.11 Protection against discharging after d.h.w. heating ........ 196 6.12 Buffer storage tank operation.............. 197 8/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Contents 26.03.2001...
Page 9
Supplementary information on the plant types listed.......210 Legend to plant types ................211 Electrical connections ................212 Dimensions ..................213 8.1.1 Panel cut-out ..................213 8.1.2 Combination of controllers ..............213 Technical data..................214 9/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Contents 26.03.2001...
• Protection against boiler overtemperatures (pump overrun) • Adjustable minimum and maximum limitation of boiler temperature (boiler flow temperature) • Burner cycling protection by observing a minimum burner running time 10/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Summary 26.03.2001...
Page 11
• Logging the number of burner starts of stages 1 and 2 • Logging the flue gas temperature • Display of plant diagram no. Not with RVA53.242 11/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Summary 26.03.2001...
“Local Process Bus (LPB), Basic Documentation, System Engineering“ (document no. CE1P2370E) must be satisfied • The local regulations (for installation, etc.) must be complied with 13/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Summary 26.03.2001...
• Plug the connectors into the respective sockets at the rear of the controller è Note: The connectors are coded to make certain they cannot be mixed up. 14/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Handling 26.03.2001...
Page 15
Note: Tighten the screws only slightly, applying a torque of maximum 20 Ncm. When tightening the screws, the fixing levers automatically assume their correct positions. 15/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Handling 26.03.2001...
30° and there must be a clearance of at least 10 mm above and below the cooling slots. This allows the controller to emit the heat generated during operation. 16/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Handling 26.03.2001...
2.2.2 Wiring When using prefabricated cables with connectors, the electrical installation is very straightforward, owing to coding. Note Rear of controller Connection terminals of RVA63.242 2373A01 Connection terminals of RVA53.242 2373A10 17/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242...
Page 18
Burner stage 2 Phase burner stage 2 Burner stage 1 Phase burner stage 1 Live AC 230 V (mains connection) AGP3S.02D black Neutral (mains connection) 18/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Handling 26.03.2001...
• Note: If no button is pressed for about 8 minutes, the controller will automatically return to the operating mode selected last. 19/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Handling 26.03.2001...
Page 20
Display The pointer below the symbol indicates the output activated The number indicates the current test step The number indicates the selected setting line 20/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Handling 26.03.2001...
Page 21
The selected sensor values are updated within a maximum of 5 seconds. Note An open-circuit is displayed as – – –. A short-circuit is displayed as o o o. 21/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Handling 26.03.2001...
Page 22
Display The number indicates the current test step Displayed value of the temperature measured The number indicates the selected setting line 22/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Handling 26.03.2001...
"End-user”. display • Note: If no button is pressed for about 8 minutes, the controller will automatically return to the operating mode selected last. 23/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Handling 26.03.2001...
"Heating engineer”. display è Note: If no button is pressed for about 8 minutes, the controller will automatically return to the operating mode selected last. 26/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Handling 26.03.2001...
-50...+50 °C (TAxged) Composite outside temperature -50...+50 °C (Taxgem) Outside temperature source - -:- / 00.01...14.16 - - . - - No signal 00.01...14.16 Address 27/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Handling 26.03.2001...
Page 28
Pump function output (K7) 0...7 No function Heating circuit pump D.h.w. circulating pump Electric immersion heater for d.h.w. Solar pump Pump H2 Boiler bypass pump Alarm output 28/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Handling 26.03.2001...
Page 29
0 / 1 Inactive Active Gain of locking signal 0...200 Floor curing HK1 0...3 Functional heating Floor curing heating Functional and floor curing heating D.h.w. 29/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Handling 26.03.2001...
Page 30
In the segment In the system (if segment address = 0) Automatic summer / winter changeover 0 / 1 Local change Central changeover of all heating circuits 30/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Handling 26.03.2001...
Page 31
This line is active only if the unit is addressed as the heat generation master. Also refer to "LPB device address" in Index. This setting is not integrated for RVA53... 31/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Handling 26.03.2001...
Whether correct or incorrect, each push of a button will be adopted as a digit of the code. As a confirmation, the respective digit changes to 1. 32/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Handling...
Gain factor of room influence (KORR) 0...20 Constant for quick setback and optimum start 0...20 control (KON) Boost of the room temperature setpoint (DTRSA) 0...20 °C (K) (with boost heating) 33/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Handling 26.03.2001...
Page 34
Continuously Partly Service Continuous display 0 / 1 Weekday / time of day Actual value of boiler temperature Software version 00.0...99.0 Device operating hours 0...500000 34/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Handling 26.03.2001...
Function button with LED for manual operation Function button with LED for Activation of chimney sweep function chimney sweep Diagnostics and service Connection facility for PC tool 35/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Handling 26.03.2001...
Page 36
Symbols - indication of operating state with the black pointers Display during normal control mode or when making settings Programming line when making settings Heating program of current day 36/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Handling 26.03.2001...
It must be above the TKmax setting • Check setpoint of the d.h.w. temperature • Check actual value of the d.h.w. temperature • Check if d.h.w. heating is released 37/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Handling 26.03.2001...
Page 38
• Check the sensor connected to A6 (input test) Fault status signal; display shows "ER" • For cause of error, refer to section "Parameter settings for end-user" on line 50 38/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Handling 26.03.2001...
• Protective functions active • Changeover on room unit inactive • Automatic summer / winter changeover (ECO functions) and automatic 24-hour heating limit active 39/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
Page 40
Changeover of the operating mode on the room unit is active only when the controller is in automatic mode The room temperature is transmitted to the controller via PPS, independent of the selected operating mode. 40/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
• Assignment of d.h.w. heating • Reduced setpoint of the d.h.w. temperature • D.h.w. heating program • D.h.w. heating • Type of d.h.w. demand 41/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
During the heating periods, the nominal room temperature setpoint is maintained. The heating periods are in accordance with the settings made on lines 6 through 11 and 13 through 18. 42/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
Setpoint adjustment on the room unit’s line 19 °C Adjustment made with the controller’s setpoint knob + 2 °C Resulting setpoint 21 °C 43/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
In the case of a BMU, the loads will immediately be released. Display 44/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
The following functions are no longer active in manual operation: maximum limitation of the boiler temperature: Maintained return temperature with mixing valve Display 45/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
The time switch will be set to the selected weekday. This setting is important to make certain the controller’s heating program will operate correctly. Monday Friday Weekday table Tuesday Saturday Wednesday Sunday Thursday 46/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
The year of the controller will be based on this setting. This setting of year is important to make certain the controller’s holiday program and summer- / wintertime changeover will operate correctly. 47/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
First, choose the 7-day block (1-7) to enter the switching times that apply to the majority of days; then, select the individual days (1...7) to make the required adjustments. 48/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
Page 49
Example: 24 h 49/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
In AUTO mode, the time switch program can be set on both the controller (as described Effect of room unit above) and on the QAA70 room unit. It is always the last action that is active. 50/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
Entry of switching times on lines 13 through 18 is made only for the individual day selected here. Example: For an example, refer to the graph in the previous section “Time switch program 1". 51/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
Effect of room unit works only if automatic mode is selected on the controller. Also refer to "room unit values" in Index. 52/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
Entry of the switching times on lines 20 through 25 is made only for the individual day selected here. Example: For an example, refer to the graph in the previous section “Time switch program 1". 53/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
D.h.w. program The times at which these d.h.w. setpoints shall apply can be set with the d.h.w. program on line 121. 55/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
Example: The heating periods are in accordance with the settings made on lines 6 through 11. 2373Z11 24 h 56/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
THG +1 °C THG -1 °C Changeover between summer and winter operation TAged Attenuated outside temperature Summer / winter changeover temperature Temperature Time Heating 58/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
Comfort is considerably enhanced when using a room sensor. 27,5 22,5 °C 17,5 12,5 °C Heating circuit diagram Flow temperature Composite outside temperature 59/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
Setting range Unit Factory setting 8...30.0 °C For detailed information about changeover, refer to “Summer / winter changeover temperature heating circuit 1" (THG1). 60/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
The flow temperature setpoint determined in this way serves as a setpoint request for Flow temperature setpoint generating the boiler temperature setpoint. Also refer to "generation of boiler temperature setpoint" in Index. 61/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
For more detailed information about resetting the attenuated outside temperature to the actual room temperature, refer to "attenuated outside temperature" in Index. 62/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
This information makes it possible to determine if: − the plant is correctly sized − the burner has become dirty 63/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
The number of burner starts is written to non-volatile memory at 2-hour intervals or whenever there is a power failure. 64/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
The number of burner starts is written to non-volatile memory at 2-hour intervals or whenever there is a power failure. 65/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
Effect with room unit: The holiday function of the room unit is taken into consideration but the entries made on the controller have priority. 67/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
Setting Display Unit 1...8 – 3.31 Start and end of holiday period heating circuits 1 and 2 Setting Display Unit 01.01...31.12 Day.Month 68/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
The BMU displays error code 175. Note If there is a BMU error code, operating line 50 also displays a general BMU fault (error code 150). 69/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
Address collision on LPB (same address several times) Short-circuit PPS 2 clock masters present Inadmissible LPB device or segment number Inadmissible plant configuration General BMU fault Fault contact H2 70/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
Page 71
Display Example of a display after a fault has occurred: “ER“ indicates that a fault has occurred. Press to indicate the faults. 71/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of end-user settings 26.03.2001...
Display of input H1 according to the function selected on line 170 [°C / 000 / - - -] Test step 10 Display switching state input E1 73/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Setting operating line “Heating curve slope HK2” (line 32) - or value between 2.5 and − Setting the type of heat source (line 80) 74/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
If the controller is used in a zone, it is the actual value delivered via LPB. Setting Display Unit 0...140 °C 75/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Unit 0...140 °C Note If only one d.h.w. temperature sensor is connected, lines 61 and 62 will show the same value. 76/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
To be used as a collector temperature sensor, input B8/B6 must be appropriately defined (line 99). Setting Display Unit 0...350 (Pt 1000) °C 0...230 (Ni 1000) 77/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Address of outside sensor The first 2 digits represent the segment number (01.) The second 2 digits represent the device number (.02) 78/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
No setpoint is displayed (---) when there is no heat demand from the consumers. 79/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings...
Also refer to "nominal room temperature setpoint" in Index. 80/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Function and effect of this setting are basically the same as with setting 73 described above. Setting Range Unit 0...35 °C 81/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
The current values of the floor curing function are displayed here. The function itself is activated under setting 116. Setting Display Unit (Inactive) 0...32 0...95 Example 82/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
For burner control, minimum limitation of the burner running time is considered to ensure no unnecessary cycling takes place in part load operation. 83/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings...
Page 84
Reset integral modulation (reset integral second stage “2-stage burner”) Neutral zone On / off pulses Basic stage Modulating stage Switching differential boiler Boiler temperature setpoint 84/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Page 85
Note assignment: K4?K6 Important K5?K7 The functioning for switching the first and second boiler corresponds to that of 2-stage burner operation. 85/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Boiler temperature °C Boiler temperature setpoint Tkmin Minimum limitation of the boiler temperature Switching differential TAgem Composite outside temperature mi n °C 86/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
When automatic summer / winter changeover of the pump heating circuit has responded, extra heating for the bathroom will also be switched off. 87/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings...
With the cascade “2 times single-stage”, this setting line is inactive since in this Important application K6 is controlled fix as the boiler pump. 88/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Page 89
The setting for this function must be made on line 122. Also refer to "switching program selection circulating pump" in Index. 89/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Page 90
It is possible to select different modes of control for the boiler pump. Also refer to "control of boiler pump" in Index. 90/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings...
Page 91
When the error is corrected, that is, which means that the error message is no longer present, the contact will open with no delay. 91/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings...
If the second heating circuit is used for extra heating for the bathroom, also refer to bathroom setting line “extra heating for the bathroom” in Index. 92/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Page 93
24.00 hrs on the day of change to avoid potential interruptions caused by utility locking periods. 93/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings...
Page 94
When the fault is corrected, that is, when the fault status is no longer present, the relay will be deenergized with no delay. 94/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings...
Each setpoint readjustment, be it via the setting value or the operational level, is a parallel displacement of the heating curve. °C °C Flow temperature Composite outside temperature Room temperature setpoint 96/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
• There may be no controlled thermostatic radiator valves in the reference room. (If such valves are present, they must be set to their fully open position). 97/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings...
Room temperature setpoint Switching differential of room temperature Setpoint Switching differential of the room temperature Switch-on point Switch-off point °C 98/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Otherwise, the settings made on the room unit will be inactive. Display As soon as the operating mode on the room unit is changed, the controller's automatic button will flash. 99/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
The heating circuits are located in partly separate spaces or flats. Plant type Location of heating circuits Line 103 Line 104 21/22/23/24 Not in the same space 100/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Page 101
This means that the room unit values shall only act on heating circuit 2. Plant type Location of heating circuits Line 103 Line 104 21/22/23/24 In the same space 101/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
The associated maximum limitation of the flow temperature setpoint is line 108. Setting Setting range Unit Factory setting 8...TVmax °C 102/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Function and action of this setting are basically the same as with setting 107 described above. Setting Setting range Unit Factory setting TVmin...95 °C 103/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Optimization calculates the changeover time such that, at the start of occupancy, the room temperature will have reached the nominal setpoint. 104/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Page 105
- 0.25 K. The correct switch-on time is determined by adaption. 105/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
10 minutes (earlier shut-down). In the other case, the switch-off point is shifted backward by 10 minutes (later shut-down). 106/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings...
Building construction Heavy building structures : Buildings with thick walls or with external insulation Light building structures: Buildings with a light envelope 107/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
1. In this temperature range, the readjustment of the slope is weighted with factor f2 and adaption sensitivity 1. 108/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
100 % Locking signal will be adopted unchanged 101...200 % Locking signal will be considered up to twice the normal signal 109/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
The following graph shows the temperature profile of the selected floor curing function. [TVw] [Tag Fh + Bh Flow temperature setpoint Start day Functional heating Floor curing heating 110/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Page 111
The following events cause abortion of the floor curing function: The selected floor curing function is completed. Setting parameter “Floor curing function” is set to active. 111/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Switching times The periods of time during which these d.h.w. temperature setpoints shall be used can be set in the d.h.w. program. 112/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Setting 0 The d.h.w. temperature is continuously maintained at the nominal d.h.w. temperature setpoint, independent of any time switch programs. Example: 113/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Page 114
With this d.h.w. heating program, it is possible to have a maximum of three heating periods per day. There is no forward shift of the switch-on times. Example: 114/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
The circulating pump does not follow any forward shift. This means it is operated in accordance with the times of usage. 115/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
This means that even if the d.h.w. would have to be heated according to the d.h.w. program (line 121), the holiday function may lock d.h.w. heating. Only the frost protection function will remain active. 116/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
The number of d.h.w. charging cycles will not be limited. With this setting, the switch-on point is shifted forward by 1 hour (against the heating circuit's on times). 117/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings...
• The boost of the flow temperature setpoint of d.h.w. must be a minimum of 10 °C (has an impact on the charging time). • In that case, frost protection for d.h.w. is not ensured 118/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Setting on line 126 Boost Total Boiler temperature setpoint Note For d.h.w. control, refer to “switching differential of d.h.w.” in index. 119/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Depending on the consumer, the locking signal will lead to switching on / off or a setpoint reduction. 120/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Page 121
This means that if the undershoot is significant, the setpoint reduction will be greater. 121/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings...
Page 122
Start of d.h.w. heating boiler temperature Boiler temperature setpoint Actual value of the boiler temperature Switching differential of the boiler Time Locking signal 122/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
(setting 121). Also refer to "plant diagram 3" in Index. D.h.w. heating is not possible in manual operation since the diverting valve used is not controlled to provide space heating. 123/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
− Parameter "Separate d.h.w. circuit” must be set to ON. − Paramter "D.h.w. controlling element" must be set to diverting valve. 124/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Lag boiler lead boiler t [h] Total number of operating hours of all lead boilers [h] Total output of cascade [kW] 125/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Flow temperature setpoint of cascade TVKx Actual value of cascade flow temperature Time Time of release Switching differential of the boiler 126/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Reset integral for boiler sequence TVKw Flow temperature setpoint of the cascade TVKx Actual value of cascade flow temperature Time Time to reset 127/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
(address 1). Note Addressing is part of engineering. For detailed information, refer to LPB System Engineering, Basic Documentation (reference number CE1P2370E). 128/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
The design of the bus system is part of engineering. For detailed information, refer to LPB System Engineering, Basic Documentation (reference number CE1P2370E). 129/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings...
The setting is of importance only if the controller is defined as the master and located in segment 0 (address 0/1). With any other addressing, it has no effect. 130/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings...
1 is used for all heating circuits. Segment address Effect According to the setting made on line 145 1...14 Throughout the segment 131/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Display If the central stand-by circuit is activated, the stand-by button on all controllers in the selected range of action flashes. 132/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Adjustment the same time, adjust the system time. Controller time System time The controller's time settings are used for the system. 133/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
For that purpose, the time of day is shifted backward by one hour. Setting Setting range Unit Factory setting 01.01...31.12. tt.MM 25.10. 134/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
These peripheral devices can only be operated under the respective PPS address. Important When connecting a room unit type QAA10, the right polarity of the terminals must be observed. 135/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
If the differential of collector temperature and storage tank temperature is smaller than temperature differential (TsdAus), the collector pump will be deactivated. 136/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings...
This enables the storage tank to be charged only from a certain collector temperature (temperature level for solar plus TSdEin). 137/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings...
The charging pump will be deactivated when the storage tank temperatures at the bottom and at the top have exceeded the maximum charging temperature (line 163). 138/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings...
This is accomplished by sending a heat demand signal to the heat source (single boiler or cascade). 139/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
When using terminal H1 as a voltage input (setting 4), it is not possible to connect several signals in parallel. 140/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Page 141
Check Buttons or + flash on all controllers in the same segment 141/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Page 142
Chimney sweep function switched on. Notes Optimally, this function can also be accomplished with the help of terminal H2 and setting line 174. 142/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Page 143
(operating line 172, setting range 5...130 °C). The voltage corresponding to the displayed temperature can then be calculated as follows: ° " * actual temperatur e" ° " Maximum value heat demand" 143/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Minimum setpoint of flow temperature, contact H, (setting on line 171) Switching differential of the boiler temperature (setting on line 3 144/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
Input H1 is used for a heat demand signal DC 0…10 V (line 170, setting 4). − Input H2 is used for d.h.w. sensor 2 (B41) or buffer storage tank sensor 2 (B41). 145/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings 26.03.2001...
In the case of d.h.w. storage tank charging with solar energy, it is important to have sensor B3 is located at the top of the storage tank and sensor B31 at the bottom. 146/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings...
Page 147
In the case of buffer storage tank charging with solar energy, it is important to have sensor B4 located at the top of the storage tank and sensor B41 at the bottom. 147/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of heating engineer settings...
Boiler temperature °C Boiler temperature setpoint Tkmin Minimum limitation of boiler temperature Switching differential TAgem Composite outside temperature mi n ° C 148/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
The greater the demand for heat, the longer the burner runs at a time. Switching differential Setpoint Switching differential of the boiler Switch-on point Switch-off point °C 149/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
The second burner stage will be activated and deactivated according to the following settings: • Release integral Setting 05 • Reset integral Setting 06 150/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
Burner Release counter Switching differential of the boiler tBRmin Minimum burner running time Boiler temperature setpoint Actual value of boiler temperature 151/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
TKw+SDK/2 TKw-SDK/2 Release limit Boiler temperature setpoint Actual value of the boiler temperature Switching differential of the boiler Time Time to release 152/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
TKw+SDK/2 TKw-SDK/2 Reset limit Boiler temperature setpoint Actual value of the boiler temperature Switching differential of the boiler Time Time to reset 153/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
5.8.1 Extended burner running time Without extended burner running time With extended burner running time °C °C TKmin TKmin -20 °C TAgem -20 °C TAgem 155/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
15 minutes. On completion of the 15 minutes, protective boiler start-up will become active again as soon as the boiler temperature gradient turns positive. 157/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
Actual value of boiler temperature Tkmin Minimum limitation of the boiler temperature Boiler switching differential (factory setting = 8K) Time Locking signal 158/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
The boiler pump operates when there is a demand for heat or when the burner operates. In that case, the boiler pump does not respond to locking signals (protective boiler start-up). 159/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
~ 300 ms 30 s – 59.5 s ~ 500 ms 60 s – 119.5 s ~ 1.10 s >120 s ~ 2.20 s 160/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
Tv influences the controller’s D-behavior. If Tv = 0, the controller has no PI behavior. Effect Note For setting rules concerning Xp, Tn and Tv, refer to section "Modulating burner control – setting rules" 161/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
More on / off pulses and shorter intervals between full load and basic load. Switching differential Setpoint Switching differential damper actuator Switch-on point Switch-off point Actual value of boiler temperature °C 162/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
(TKRmin), the boiler temperature the return temperature is used. This function necessitates a return sensor. 163/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
2-position control provides mixing by the bypass pump in the form of pulses. The extent of mixing is dependent on the mass and the amount of water in the boiler circuit. 164/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings...
In general: Burner Bypass pump OFF (on completion of the pump overrun time) Example: Burner Bypass pump Pump overrun time 165/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
Actual boiler return temperature TKRmin Minimum limitation of boiler return temperature (setting line 22 SDBP Switching differential of bypass pump (setting line 23 166/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
Page 167
This means that when the undershoot is significant, the setpoint reduction will be greater. 167/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings...
Return temperature TKRx Actual boiler return temperature TKRmin Minimum limitation of boiler return temperature Switching differential fixed = 2 K Time Locking signal 168/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
Flow temperature setpoint Setting on line 30 Boost Total Boiler temperature setpoint Note Also refer to "heating curve slope" in Index. 169/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
Shorter setback and forward shift times. For light and poorly insulated buildings that cool down quickly and that require shorter heating up times. 170/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
Also refer to “quick setback with room temperature influence” in Index. 5.23.2 Optimum start control without influence Also refer to "optimum start control" in Index. 171/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
The boost produces an increase in the flow temperature setpoint. °C Actual value of the room temperature Room temperature setpoint Setpoint boost Time 172/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
-4 °C and is switched on / off only when the outside temperature is higher takt TA °C 173/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
With this control mode, the switching differential need not be adjusted since the 3- position actuator can stop in any position. 174/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
Pump continuously OFF Notes If a flow sensor is connected (mixing heating circuit), overtemperature protection for the heating circuit pump is inactive. 176/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
The process of heating curve adaption is described in the relevant section. Also refer to curve "adaption of heating curve" in Index. 177/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
The process of heating curve adaption is described in the relevant section. Also refer to Adaption of heating curve "adaption of heating curve" in Index. 178/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
Setting "Nominal setpoint of the d.h.w. temperature” Setting "Reduced setpoint of the d.h.w. temperature” Setting "Maximum nominal setpoint of the d.h.w. temperature” 180/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
TBWx of both sensors TBWw Note If the d.h.w. temperature is controlled with 2 sensors, the respective setting must be made on line 174. 182/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
In large plants, it must be ensured that the water outlet temperature is not lower than 60 °C and that the temperature in the piping system does not drop by more than 5 °C. 183/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings...
If the boost value is less than 1/8 of the value set, d.h.w. heating will be interrupted (pump will overrun for at least 1 minute) 1 min 184/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings...
The number of operating hours cannot be reset. 185/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Description of OEM settings 26.03.2001...
Flow temperature setpoint of heating circuit 1 (incl. setpoint boost if any) TVw2 Flow temperature setpoint of heating circuit 2 (incl. setpoint boost if any) 186/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division General control processes 26.03.2001...
(line 22 ) within the “bypass pump switching differential” (line 23 ) with the help of the bypass pump in on / off operation. 187/218 Siemens Building Technologies Basic Documentation RVA53.242, RVA53.242 CE1P2373E Landis & Staefa Division General control processes...
A new readjustment should be made only after the control action resulting from the previous readjustment is completed. 188/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division General control processes 26.03.2001...
Increase Tv in steps of 2 to 5 seconds. Increase Tv in steps of 10 to 20 seconds. Repeat steps 2 and 3 alternately. 189/218 Siemens Building Technologies Basic Documentation RVA53.242, RVA53.242 CE1P2373E Landis & Staefa Division General control processes...
Process The temperature basis used for this process are the values of the flow temperature setpoint and the current room temperature setpoint. 190/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division General control processes 26.03.2001...
Page 191
• Heating’s switch-on point 31OEM ≥ − TVwk TVwk Flow temperature setpoint readjusted by the room influence Room temperature setpoint Slope of heating curve 191/218 Siemens Building Technologies Basic Documentation RVA53.242, RVA53.242 CE1P2373E Landis & Staefa Division General control processes 26.03.2001...
If the flow temperature exceeds the limit value “Maximum limitation of flow temperature” + 7.5 °C (fixed value), the pump will be deactivated. This limit function acts only with the mixing heating circuit. 192/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division General control processes 26.03.2001...
The attenuated outside temperature acts indirectly, via the composite outside temperature, on flow temperature control. Example TAakt °C TAged 18:00 06:00 18:00 06:00 18:00 TAakt Actual outside temperature TAged Attenuated outside temperature 193/218 Siemens Building Technologies Basic Documentation RVA53.242, RVA53.242 CE1P2373E Landis & Staefa Division General control processes 26.03.2001...
Actual outside temperature TAged Attenuated outside temperature TAgem1 Composite outside temperature for light building structures TAgem0 Composite outside temperature for heavy building structures 194/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division General control processes 26.03.2001...
· SDBW TBWw TBWR Push SDBW Switching differential d.h.w. TBWw Nominal setpoint of the d.h.w. temperature TBWR Reduced setpoint of the d.h.w. temperature 195/218 Siemens Building Technologies Basic Documentation RVA53.242, RVA53.242 CE1P2373E Landis & Staefa Division General control processes 26.03.2001...
(common flow temperature) or, in certain situations, with the boiler temperature. If the cascade temperature (or the boiler temperature) is lower than the storage tank temperature, pump overrun will be stopped prematurely. 196/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division General control processes 26.03.2001...
The diverting valve must be connected in parallel to the pump of the boiler. The pump valve must be defined as a boiler pump (refer to operating line 95). 197/218 Siemens Building Technologies Basic Documentation RVA53.242, RVA53.242 CE1P2373E Landis & Staefa Division General control processes 26.03.2001...
Reasons for an invalid demand for heat can be, for example:summer / winter changeover, 24-hour heating limit, quick setback, or room temperature limitation by room sensor. 198/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division General control processes 26.03.2001...
) is taken into consideration • Pump overrun will be activated when d.h.w. heating is terminated • This function is not available when heating the d.h.w. with a control thermostat 199/218 Siemens Building Technologies Basic Documentation RVA53.242, RVA53.242 CE1P2373E Landis & Staefa Division General control processes 26.03.2001...
5 minutes. This ensures that the hot water will reach the entire heating circuit including the return. 200/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division General control processes 26.03.2001...
C of the relevant table. Note The graphic presentations of the plant types always correspond to the possible full use of the grouping given. 201/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Application examples 26.03.2001...
K5/K7 Y1/Y2 Important RC members for suppression of interference and for protection of relay contacts K5 and K7 must be fitted externally. 203/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Application examples 26.03.2001...
7.3.2 System pump before d.h.w. Heat source variant Plant type D.h.w. a) c) a) c) a) c) a) c) a) c) 206/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Application examples 26.03.2001...
In the case of BMU applications (B1) with d.h.w. heating by the BMU, this plant type is also shown. With this application, setting “D.h.w. priority” of the RVA63 is not active. 210/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Application examples 26.03.2001...
(e) gives the total length of the panel cut-out. Example Combination Calculation Panel cut-out 96 plus 96 96+96-4 188 mm 144 plus 96 96+144-5 235 mm 144 plus 144 144+144-6 282 mm 213/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Dimensions 26.03.2001...
(H1, H2), and d.h.w. control thermostat (gold-plated contacts) Weight of controller approx. 0.6 kg Miscellaneous Clock reserve min. 12 h 214/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Technical data 26.03.2001...
Page 215
DC 0...10 V demand for heat with reduced d.h.w. setpoint ..139 ..............145 device operating hours ........185 mixing valve restriction 215/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Index 26.03.2001...
Page 216
∆T control ............137 reduction of condensation........156 energy-related..........137 regulations for installation ........14 release integral for boiler sequence..... 126 level-related..........137 release integral for boiler sequence..... 126 216/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Index 26.03.2001...
Page 217
Complete document number of existing functions have been modified and adapted. It is therefore not possible to give a detailed description of all the changes made. 217/218 Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E Landis & Staefa Division Korrigenda 26.03.2001...
Need help?
Do you have a question about the RVA63.242 and is the answer not in the manual?
Questions and answers