7 ONLINE MODULE CHANGE

7.3 Online Module Change Procedure

7.3.1 When factory setting is used and initial setting was made with GX Configurator-TI

7 - 3
There are the following online module change procedures depending on whether the
user range setting has been made or not, whether the initial setting of GX Configurator-
AD has been made or not, and whether the other system exists or not.
Range setting
Factory setting
Factory setting
User range setting
User range setting
User range setting
User range setting
(1) Conversion disable
(a)
Set Conversion enable/disable designation (buffer memory address 0:
Un\G0) for all channel conversion disable and turn the operation condition
setting request (Y9) from OFF to ON to stop conversion.
Initial setting
GX Configurator-TI
Sequence program
GX Configurator-TI
GX Configurator-TI
Sequence program
Sequence program
MELSEC-Q
Other system
Reference section
Section 7.3.1
Section 7.3.2
Present
Section 7.3.3
Absent
Section 7.3.4
Present
Section 7.3.5
Absent
Section 7.3.6
7 - 3