7 ONLINE MODULE CHANGE

7.3 Online Module Change Procedure

7.3.1 When industrial shipment setting is used and initial setting was made with GX
Configurator-AD
7 - 4
There are the following online module change procedures depending on whether the
user range setting has been made or not, whether the initial setting of GX Configurator-
AD has been made or not, and whether the other system exists or not.
Range setting
Industrial shipment setting GX Configurator-AD
Industrial shipment setting Sequence program
User range setting
User range setting
User range setting
User range setting
(1) Conversion disable
(a)
Set the A/D conversion enable/disable setting (buffer memory address 0:
Un\G0) for all channel conversion disable and turn operating condition
setting request (Y9) from OFF to ON to stop conversion.
After confirming that conversion has stopped with the A/D conversion
completion flag (buffer memory address 10: Un\G10), turn off Operation
Condition Setting Request (Y9).
(The screen shows the setting example of the Q64AD-GH.)
Initial setting
GX Configurator-AD
GX Configurator-AD
Sequence program
Sequence program
MELSEC-Q
Other system
Reference section
Section 7.3.1
Section 7.3.2
Present
Section 7.3.3
Absent
Section 7.3.4
Present
Section 7.3.5
Absent
Section 7.3.6
7 - 4