Lenovo Flex System x220 Installation And Service Manual page 338

Compute node
Hide thumbs Also See for Flex System x220:
Table of Contents

Advertisement

Automatically notify support
No
Alert Category
Critical - Temperature
SNMP Trap ID
0
CIM Information
Prefix: PLAT ID: 0524
User Response
Complete the following steps until the problem is solved: 1. Check the Chassis Management Module
or Flex System Manager event log for any fan- or cooling-related issues. 2. Make sure that the
airflow at the front and rear of the chassis is not obstructed and that fillers are in place and correctly
installed. 3. Make sure that the room temperature is within operating specifications. 4. If there are no
other thermal issues, replace the PCIe Card.
80070301-3702ffff : Sensor PEN Inlet Over T has transitioned to non-recoverable from a less
severe state.
The PCIe Expansion Node Inlet temperature has exceeded its specified threshold. The compute node has
attempted a soft shutdown.
May also be shown as 800703013702ffff or 0x800703013702ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Temperature
SNMP Trap ID
0
CIM Information
Prefix: PLAT ID: 0524
User Response
1. Check the Chassis Management Module or Flex System Manager event log for any fan- or
cooling-related issues. 2. Make sure that the airflow at the front and rear of the chassis is not
obstructed and that fillers are in place and correctly installed. 3. Make sure that the room temperature
is within operating specifications.
• 80070319-2201ffff : Sensor S3 Resume Fail has transitioned to non-recoverable from a less severe
state.
The S3 Resume Fail sesor has transitioned to non-recoverable from less severe.
May also be shown as 800703192201ffff or 0x800703192201ffff
330
Flex System x220 Compute Node Installation and Service Guide